Publication 1756-UM050A-EN-P - December 2001
8-4
Interfacing with FLEX I/O
Configure the I/O
You now add the FLEX I/O modules to the controller’s I/O
configuration. To do this you first add the local 1756-ENBT module to
the I/O configuration. Next you add the 1794-AENT adapter as a
“child” of the 1756-ENBT module. Then you add the I/O modules as
“children” of the 1794-AENT adapter.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1.
Select the
IO Configuration
folder in the project window and
click the right mouse button.
The following pop-up window will open.
2.
Click on
New Module
.
IMPORTANT
Click on the
Help
buttons on the configuration
screens shown in this section if you need assistance
in selecting and setting the parameters.