Publication 1756-UM050A-EN-P - December 2001
5-2
Using Rack Optimized I/O
Set Up the Hardware
For this example, one ControlLogix chassis contains a Logix 5550
controller in slot 0 and a 1756-ENBT module in slot 1. A second
chassis contains a 1756-ENBT module in slot 0 and the I/O modules in
slots 1 and 2.
To work along with this example set up your system as shown above.
•
Note that in the example application, the Logix5550 controller,
I/O modules, and the 1756-ENBT modules are in the slots
shown above.
•
Verify the IP addresses for your PC and 1756-ENBT modules
(see chapter 4).
•
Verify that all wiring and cabling is properly connected.
•
Make sure you have your communication driver (e.g.,
AB_ETH-1) configured in RSLinx as described in Appendix C.
Data
Slot 0 1
Slot 0 1 2
Switch
Programming
130.130.130.1
Terminal
Local
Chassis
Remote
Chassis
1756-IB16I
Digital Input
1756-OB16I
Digital Output
Logix5550
Controller
1756-ENBT
130.130.130.2
1756-ENBT
130.130.130.3
Summary of Contents for ControlLogix 1756-ENBT
Page 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Page 4: ......
Page 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Page 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Page 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Page 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Page 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Page 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Page 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Page 143: ...AB Parts...