Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
9
Preface
This safety reference manual is intended to do the following:
•
Describe the ControlLogix Control System components available from
Rockwell Automation that are suitable for use in low-demand,
safety-related control, up to and including SIL 2 applications
•
Provide safety-related information specific to the use of ControlLogix
modules in SIL 2 systems - including PFD calculations that need to be
considered for SIL 2-certified systems
•
Explain some possible SIL 2-certified system configurations
•
Describe basic programming techniques for the implementation of
ControlLogix SIL 2-certified systems with references and links to
more-detailed programming and implementation techniques
Terminology
This table defines abbreviations used in this manual.
IMPORTANT
This manual describes typical SIL 2 implementations using certified
ControlLogix equipment. Keep in mind that the descriptions presented in this
manual do not preclude other methods of implementing a SIL 2-compliant
system by using ControlLogix equipment.
Other methods should be reviewed and approved by a recognized certifying
body, such as TÜV Rheinland Group.
Table 1 - Abbreviations Used throughout This Reference Manual
Abbreviation
Full Term
Definition
CIP
Common Industrial
Protocol
A industrial communication protocol used by Logix5000™-based
automation systems on Ethernet, ControlNet, and Devicenet
communication networks.
CL
Claim Limit
The maximum level that can be achieved.
DC
Diagnostic Coverage
The ratio of the detected failure rate to the total failure rate.
EN
European Norm.
The official European Standard.
GSV
Get System Value
A ladder logic instruction that retrieves specified controller
information and places it in a destination tag.
MTBF
Mean Time Between
Failures
Average time between failure occurrences.
MTTR
Mean Time to Restoration
Average time needed to restore normal operation after a failure has
occurred.
PADT
Programming and
Debugging Tool
RSLogix™5000 software is used to program and debug a SIL 2-certified
ControlLogix application.
PC
Personal Computer
Computer used to interface with, and control, a ControlLogix system
via RSLogix 5000 programming software.
PFD
Probability of Failure on
Demand
The average probability of a system to fail to perform its design
function on demand.
PFH
Probability of Failure per
Hour
The probability of a system to have a dangerous failure occur per hour.
SIL
Safety Integrity Level
A discrete level for specifying the safety integrity requirements of the
safety functions allocated to the electrical/electronic/ programmable
electronic (E/E/PE) part of the safety system.
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...