ControlLogix I/O Modules
Chapter 5
Wiring the Single-ended Input Module in Current Mode
Make sure you:
•
Using Analog Input Modules on page 47
•
use the correct documentation (listed in
Additional Resources on page 10
to wire the module.
•
place devices correctly in the current loop. You can locate other devices in
an input channel’s current loop anywhere as long as the current source can
provide sufficient voltage to accommodate all of the voltage drops (each
module input is 250 ohms)
shows how to wire the 1756-IF8 module for use in Current mode.
Figure 23 - ControlLogix Analog Input Module Wiring in Current Mode
Wiring the Thermocouple Input Module
Make sure you:
•
Using Analog Input Modules on page 47
•
use the correct documentation (listed in
Additional Resources on page 10
to wire the module.
•
wire to same input channel on both modules. When wiring
thermocouples, wire two in parallel to two modules. Use the same channel
on each module to make sure of consistent temperature readings.
shows how to wire the 1756-IT6I module.
Current
Source A
Ch0 +
43369
Ch0 +
Ch0 –
Ch0 –
Current
Source B