Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
121
Appendix
D
Checklists
Checklist for the ControlLogix
System
The following checklist is required for planning, programming and start up of a
SIL 2-certified ControlLogix system. It may be used as a planning guide as well as
during proof testing. If used as a planning guide, the checklist can be saved as a
record of the plan.
Topic
Page
Checklist for the ControlLogix System
Checklist for the Creation of an Application Program
Check List for ControlLogix System
(1)
Company:
Site:
Loop
definition:
No.
Fulfilled
Comment
Yes
No
1
Are you only using the SIL 2-certified ControlLogix modules listed on
, with the corresponding
firmware release listed in the table, for your safety application?
2
Have you calculated the system’s response time?
3
Does the system’s response time include both the user-defined, SIL-task program watchdog (software
watchdog) time and the SIL-task duration time?
4
Is the system response time in proper relation to the process tolerance time?
5
Have PFD values been calculated according to the system’s configuration?
6
Have you performed all appropriate proof tests?
7
Have you defined your process parameters that are monitored by fault routines?
8
Have you determined how your system will handle faults?
9
Have you taken into consideration the checklists for using SIL inputs and outputs listed on pages
and
.
(1) For more information on the specific tasks in this checklist, see the previous sections in the chapter or
.
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...