Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
109
PFD Calculations for a SIL 2 System
Appendix C
1756-L62/B
ControlLogix 4 MB controller
1,034,830
9.663E-07
2.1211E-04
—
1756-L63/B
ControlLogix 8 MB controller
1,055,910
9.471E-07
2.0788E-04
—
1756-L63XT/B
ControlLogix-XT controller
357,760
2.795E-06
6.1354E-04
—
1756-L71/B
(5)
ControlLogix 2 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-L72/B
ControlLogix 4 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-L73/B
ControlLogix 8 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-L73XT/B
ControlLogix-XT 8 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-L74/B
ControlLogix 16 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-L75/B
ControlLogix 32 MB controller
x
9,946,827
1.005E-07
4.500E-04
—
1756-CNB/E
ControlLogix ControlNet communication module
1,786,977
5.596E-07
1.2283E-04
—
1756-CNBR/E
ControlLogix redundant ControlNet communication
module
2,608,543
3.834E-07
8.4147E-05
—
1756-CN2/B
(6)
ControlLogix ControlNet communication module
x
1,096,299
9.122E-07
2.0022E-04
—
1756-CN2R/B
ControlLogix redundant ControlNet communication
module
x
1,096,299
9.122E-07
2.0022E-04
—
1756-CN2RXT/B
ControlLogix-XT ControlNet communication module
x
1,980,160
5.050E-07
1.1085E-04
—
1756-DHRIO/E
ControlLogix Data Highway Plus Remote I/O module
2,503,396
3.995E-07
8.7681E-05
—
1756-DHRIOXT/E
ControlLogix-XT Data Highway- Plus Remote I/O module
2,503,396
3.995E-07
8.7681E-05
—
1756-DNB/D
(7)
ControlLogix DeviceNet communication module
2,192,202
4.562E-07
1.0013E-04
—
1756-ENBT
ControlLogix EtherNet/IP communication module
2,022,198
4.789E-07
1.0511E-04
—
1756-EN2T/C
ControlLogix EtherNet/IP communication module
1,312,712
7.618E-07
1.6721E-04
—
1756-EN2TR/B
ControlLogix redundant EtherNet/IP communication
module
x
3,664,960
2.729E-07
5.9892E-05
—
1756-EN2TXT/C
(4)
ControlLogix-XT EtherNet/IP communication module
1,300,000
7.692E-07
1.6885E-04
—
1756-RM/B
ControlLogix System redundancy module
1,373,840
7.279E-07
1.5977E-04
—
1756-RMXT/B
ControlLogix-XT redundancy module
980,096
1.020E-06
2.2396E-04
—
1756-SYNCH
ControlLogix SyncLink module
6,932,640
1.442E-07
3.1662E-05
—
1756-IA16I
ControlLogix AC isolated input module
x
20,801,920
4.807E-08
—
1.39236E-07
1756-IA8D
ControlLogix AC diagnostic input module
x
15,966,080
6.263E-08
—
1.39265E-07
1756-IB16D
ControlLogix DC diagnostic input module
x
30,228,640
3.308E-08
—
1.39206E-07
1756-IB16I
ControlLogix DC isolated input module
x
81,443,094
1.228E-08
—
1.39164E-07
1756-IB16ISOE
ControlLogix sequence of events module
x
11,537,760
8.667E-08
—
1.39314E-07
1756-IB32/B
ControlLogix DC input module
x
10,462,329
9.558E-08
—
1.39332E-07
1756-IF8
ControlLogix analog input module
x
8,699,254
1.150e-07
—
1.3937E-07
1756-IF8H
ControlLogix HART analog input module
x
1,291,978
7.740E-07
—
1.40766E-07
1756-IF16
ControlLogix isolated analog input module
x
4,592,506
2.177E-07
—
1.39582E-07
1756-IF16H
(4)
ControlLogix HART analog input module
x
442,914
2.258E-06
—
1.44312E-07
1756-IF6CIS
ControlLogix isolated sourcing analog input module
x
2,654,080
3.768E-07
—
1.39912E-07
1756-IF6I
ControlLogix isolated analog input module
1.39626E-07
Table 10 - PFD Calculations - 1-year for ControlLogix Component
Cat. No.
(1)
(2)
Description
61508
(2010)
Mean Time Between
Failure (MTBF)
(9)
λ
(10)
Calculated PFD
1oo1
Architecture
1oo2
Architecture
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...