Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
69
FLEX I/O Modules
Chapter 6
Wiring the Single-ended Input Module in Current Mode
Requirements When Using FLEX I/O Analog Input
, before wiring the module, consider the following
application guideline:
• Place other devices in current loop
. You can locate other devices in an
input channel’s current loop anywhere as long as the current source can
provide sufficient voltage to accommodate all of the voltage drops (each
module input is 250 ohms)
Figure 40 - FLEX I/O Analog Input Wiring in Current Mode
RET
RET
RET
RET
Current
Source B
Current
Source B
Current
Source A
Current
Source A
1794-TB3
1794-TB3
1794-TB3
1794-TB3
1794-IE8
Analog Input
1794-IE8
Analog Input
1794-IE8
Analog Input
1794-IF4I
Analog Input
1794-IF4I