Table A.29 List of Event Types
Applies to:
PM3000 Type
See table
Event
Code.
M4
M5
M
6
M
8
Event type
Event Command
Code
Comment
0
•
• •
No event
0
The log starts with no events recorded
1
•
• •
Setpoint triggered
Setpoint Number
A setpoint activated
2
•
• •
Setpoint released
A previously active setpoint released
3
•
• •
Relay force energized
Relay Number
1 = Form C relay, 2 = KYZ
4
•
• •
Relay force de-energized
5
•
• •
Relay force released
6
•
• •
Status input set
Status Input Number
7
•
• •
Status input cleared
8
•
• •
KWh counter set or cleared
1
Records command action
8
•
• •
KVARh counter set or cleared
2
8
•
• •
KVAh counter set or cleared
3
8
•
• •
Ah counter set or cleared
4
8
•
• •
All energy counters cleared
5
8
•
• •
Trend log cleared
6
8
•
• •
Min/max log cleared
7
8
•
• •
Factory defaults restored
8
8
•
• •
Status input #1 counter cleared
9
8
•
• •
Status input #2 counter cleared
10
8
•
• •
Reserved
11
8
•
• •
Single setpoint timer cleared
12
8
•
• •
All setpoint timers cleared
13
9
•
• •
Power-up
0
Control power was applied.
10
•
• •
Power-down
0
Control power was lost or internal reset occurred.
11
•
• •
Selftest failure
Status Error Code
Refer to Table A.28 Status Error Codes (bitfield)
12
•
• •
Date/time set
0
The date and/or time was set or altered.
13
•
• •
Change of non-setpoint config data 0
14
•
• •
Change of setpoint config data
0
15
•
• •
NVRAM Clr
0
NVRAM has been cleared due to an extended loss
of control power or internal error.
16
•
Transient detected
17
•
User Comment
User has manually entered a comment to record the
impact of an event on your plant or process.
18
•
• •
External Demand Sync Timeout
The demand delay expired before the next expected
external demand sync
19
•
• •
Comm Card Reset
An unexpected comm card condition has been
detected and the master module has reset the
comm card in an attempt to resume normal
operation.
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...