Figure 4.11 I/O Connection Setup
Select ‘Data – INT’ as the Communications Format. Enter the IP
address of the Powermonitor 3000. Set the Connection Parameters as
shown for the default configuration. If you change the configuration
of the input assembly instance, enter its new size in Instance 1 here.
Select 3 as the Configuration instance and leave its Size set to 0 bytes
(the Series B Powermonitor 3000 does not support a Class 1
configuration connection). Click the Next> button.
Figure 4.12 Requested Packet Interval Setup
Set the Requested Packet Interval to 100 mS or greater. The
Powermonitor 3000 will not respond reliably to an RPI of less than
100 mS.
The Powermonitor 3000 data will be found in controller tags as shown
in Figure 4.13.
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...