Publication 1404-UM001D-EN-E - October 2004
A-6
Powermonitor 3000 Data Tables
Table A.3 Discrete Data
CSP File No.
N9
Remote I/O BT
10
CIP Assy. Inst.
3
No. of Elements
6
User Configurable
No
Data Type
Integer
Data Access
Read Only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Comment
0
30001
Relay output status
0 to 3
0 = De-energized & not forced
1 = Energized & not forced
2 = Force De-energized
3 = Force Energized
1
30002
Solid-state KYZ output
status
2
30003
Alarm output word
0 to FFFF Bitfield indicating state of the 16 alarm output flags; 0 = released, 1 = asserted.
Bit 0 = relay/setpoint output flag 1
Bit 1 = KYZ/setpoint output flag 2
Bit 2 = setpoint output flag 3
…
Bit 15 = setpoint output flag 16
3
30004
Status inputs state
0 to 3
Bit 0 = status input #1; 0 = open, 1 = contact closure detected
Bit 1 = status input #2; 0 = open, 1 = contact closure detected
Bit 2 = demand sync timeout; 1 = the demand delay expired before the next
expected external demand sync. This bit clears when the next external demand
sync occurs. Refer to Table A.6 Advanced Device Configuration element 23.
Bits 3-15 = unused (always 0)
4
30005
Status input #1 counter
0 to
29999
Counts to 29,999,rolls over to 0
5
30006
Status input #2 counter
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...