Publication 1404-UM001D-EN-E - October 2004
8-20
Advanced Features
•
Auto-threshold set margin:
range 1.0 to 100.0 per cent, default
20.0
•
Voltage trigger threshold:
range 0.1 to 1000.0, default 10.0
•
Current trigger threshold:
range 0.1 to 1000.0, default 10.0
Threshold Configuration
The Powermonitor 3000 compares voltage or current transients against
a threshold that you may set manually or command to be set
automatically. You select either voltage channels or current channels
with the
Detection mode
parameter.
When you issue the
Auto-threshold set command
, the Powermonitor
3000 first determines if there is sufficient signal amplitude on the
selected voltage or current channels to set the threshold. If the signal
amplitude is greater than 10% of full-scale, the Powermonitor 3000
begins timing the
Auto-threshold set duration.
During this time, it
monitors the selected channels, calculates an average transient index,
and decrements the
Auto-threshold duration time remaining
parameter
.
At the end of this time, it combines the average transient
index with the
Auto-threshold set margin
and stores the result as the
Voltage trigger threshold
or
Current trigger threshold.
Threshold settings relate to both magnitude and duration of a
transient, so they are representative of the energy contained in a
transient. In most cases, use the automatic threshold calculation as a
starting point, by issuing an
Auto-threshold set command
. Then
manually adjust the selected threshold if you want to increase or
decrease the sensitivity.
The Powermonitor 3000 will not monitor for or capture transient data
until a threshold setting has been configured.
Reading Transient Analysis Metering Data
The Powermonitor 3000 M8 model presents 12 cycles of transient
metering results for each of up to 6 transient captures in Table A.44.
Transient analysis metering data is not available via Modbus
communications. This read-only table of 14 floating-point elements
contains the following metering results and capture statistics:
•
Capture number:
transient capture number associated with the
metering results. Range 1 to 6
•
Cycle number:
which cycle in the capture is returned in this
read. Range 1 to 12
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...