Publication 1404-UM001D-EN-E - October 2004
4-8
Communications
Configuring the Powermonitor 3000 using RSNetworx for DeviceNet
1.
Launch RSNetWorx.
Table 4.4 Optional DeviceNet Communications Configuration Summary
Parameter Description
Range
Default
User
Setting
Node
Address
DeviceNet node
number (MAC ID)
0 to 64 decimal
63
Baud Rate
DeviceNet
Communications
Rate
0 = 125 Kbaud
1 = 250 Kbaud
2 = 500 Kbaud
3 = Autobaud
4 =Program Baud
0 = 125 Kbaud
Bus-off
Interrupt
Specifies response
to a CAN bus-off
interrupt
0 = Hold CAN
chip in reset
1 = Reset CAN
chip and continue
0 = Hold in Reset
TIP
DeviceNet is an open-standard, multi-vendor
communications network. Although other vendors
offer DeviceNet configuration tools, all examples in
this manual will depict the use of Rockwell Software
RSNetWorx for DeviceNet.
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...