Operation
SDI Operations & Maintenance Manual – 54264
4-27
DISCRETE INPUTS
The PLC uses the 14 discrete inputs to configure and control the mixing system.
The discrete inputs are as follows:
I-00 –
Setup mode enable
I-08 –
Stop switch
I-01 –
Pressure Scale range
I-09 –
Start switch
I-02 –
Setpoint Scale range
I-10 –
High Mixed Gas pressure switch
I-03 –
Number of venturi solenoids
I-11 –
Low vapor pressure switch
I-04 –
Number of venturi solenoids
I-12 –
Optional alarm #1
I-05 –
Number of venturi solenoids
I-13 –
Optional alarm #2
I-06 –
Number of venturi solenoids
I-14 –
Optional alarm #3
Inputs I-03 to I-06 are used for selecting the number of venturi solenoids for the
mixer.
Refer to Table 1
to determine which inputs should to be jumped to
24VDC (B3).
Table 1 - Discrete Inputs
Discrete Inputs
#of Venturi
Solenoids
I-03
I-04
I-05
I-06
0 0 0 1
1
0 0 1 0
2
0 0 1 1
3
0 1 0 0
4
0 1 0 1
5
0 1 1 0
6
0 1 1 1
7
1 0 0 0
8
All other combinations
1
0 = Input not jumped to 24vdc (B3), LED input status
OFF
(Input I-03 and I-06)
.
1 = Input jumped to 24vdc (B3), LED input status
ON
(Input I-03 and I-06)
.
Reference Electrical Drawing
.
OPTIONAL ALARM INPUTS #1 TO #3
There are 3 optional alarm inputs available that can be used to shut down the mixing
system. The alarm inputs require contacts provided by the end user.
Reference
Electrical Drawing to wire Optional Alarm Inputs #1 -3
. Optional Alarm Inputs need to
be jumped to 120VAC when not used.
NOTE: Optional Alarm input #1 has an adjustable alarm delay for Gas Quality
instruments that have dry contact outputs. Adjust potentiometer CH1 to set the timer to 0
to 10 minutes; full CCW would equal 0 seconds, middle would approximately 5 minutes,
full CW would equal 10 minutes.
Summary of Contents for VAPORAIRE M-Series
Page 8: ......
Page 18: ...Introduction 1 10 Algas SDI Operations Maintenance Manual P N 54264 Figure 7 SEQUENCER Diagram...
Page 20: ...1 12 Algas SDI Operations Maintenance Manual P N 54264 This page intentionally left blank...
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ...OPTIONS...
Page 66: ...This page intentionally left blank...
Page 68: ......
Page 69: ...APPENDIX A COMPONENT INFORMATION...
Page 70: ...This page left intentionally blank...
Page 71: ......