FIGURE 18 – Thermocouple Sensor with Bayonet Style Retainer
1) To remove a sensor fitted with the bayonet style retainer, push gently on the
retainer while turning to the left. When the retainer is disengaged, pull out the
old temperature sensor.
2) Use a short, flat-blade screwdriver to remove the adapter.
3) Install the new spring tab retainer using an appropriately sized open end
wrench (1/2” or 13mm).
4) Install the new sensor by applying a small amount of heat transfer grease to
the sensor tube and re-inserting in the unit. Squeeze the spring tab while
inserting the sensor. Push firmly until the sensor is fully engaged. There
should be at least ½” of sheath remaining.
5)
When connecting new thermocouple wires back to the control board
ensure that the yellow wires are connected to the yellow terminals and
red wires to the red terminals. Do not over tighten terminal screws!
Connect the main power wires back to the contactor and re-install the control
box lid. Torque lid bolts to 19.5 ft-lb.
Failure to properly torque lid bolts
may compromise explosion proof enclosure rating and may lead to
water entering the enclosure.
6) Restart vaporizer and check operation.
Summary of Contents for TORREXX TX100
Page 8: ......
Page 56: ...APPENDIX A TECHNICAL INFORMATION ...
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 83: ...ASCO Valve used by Algas SDI ...
Page 86: ...ASCO Valve used by Algas SDI ...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......