TORREXX Vertical Electric Vaporizer Data Sheet
LPG Systems
Refer to Nameplate on unit for the model and voltage information then look up specific information on the tables
below.
General Specifications: Applies to all units
Electrical:
50 – 60 Hz, NEMA 4, 1 Phase units are 2 wire, 3 Phase units are 3 wire
Starting Temperature: 55 Deg. C
131 Deg. F
Operating Temperature: 71-79 Deg. C 160-175 Deg. F
High Temperature Limit: 171 Deg. C
340 Deg. F
Connections:
¾” FNPT – Inlet; 1” FNPT – Outlet
Conduits:
1” FNPT, Conduit Seal-Off by others
Type of Service:
Propane Vaporization
ASME Pressure Vessel: 250 PSIG MAWP @ 250ºF
-20ºF MDMT @ 250 PSIG
Heat Exchanger Area: 2.9 ft
2
/ 0.269 m
2
TX25, TX50 and TX100
4.3 ft
2
/ 0.399 m
2
TX160
5.4 ft
2
/ 0.503 m
2
TX240
7.1 ft
2
/ 0.660 m
2
TX320
Dry Weight:
128 lbs / 58.1 kg
TX25, TX50 and TX100
145 lbs* / 65.8 kg*
TX160
155 lbs* / 70.3 kg*
TX240
173 lbs* / 78.5 kg*
TX320
*
- Add 50 lbs / 22.7 kg if vaporizer if the Mercury Relay option is installed.
Wiring:
Meets NFPA Pamphlet 70 requirements for Class I Division 1 Group D
Other:
Meets NFPA Pamphlet 58 requirements for electric vaporizers and may be
installed per indirect fired vaporizers limitations.
“TORREXX” is a trademark of Algas-SDI International LLC.
Summary of Contents for TORREXX TX100
Page 8: ......
Page 56: ...APPENDIX A TECHNICAL INFORMATION ...
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 83: ...ASCO Valve used by Algas SDI ...
Page 86: ...ASCO Valve used by Algas SDI ...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......