ASDI Operations and Maintenance – TX Models – P/N: 52368
4-20
STARTING
THE
VAPORIZER
CAUTION
Power wiring terminals may become loose during shipping. Prior to
applying electrical power all power wiring terminals must be
retightened. Recheck terminals and retighten as necessary during
next service interval.
CAUTION
Do not start the vaporizer when both inlet and outlet isolation
valves are closed. Pressure can build in the vaporizer during
startup and blow the relief valve.
1) Close the outlet isolation valve.
2) Open all valves between the storage tank and the vaporizer to allow liquid
flow to the vaporizer when the solenoid valve opens.
3) Apply power. A small “click” should be heard immediately afterwards. The
vaporizer heater elements are now energized. It will take approximately 60
seconds for the vaporizer to reach operating temperature. After reaches the
operating temperature, the Inlet Solenoid Valve will open automatically to
allow LPG to enter. Wait approximately 2 minutes so that excess LPG is
pushed back to the storage tank.
4) Carefully press the Button on top of the Liqui-SAFE
TM
valve all the way down
and SLOWLY release it. A latch mechanism inside the Liqui-SAFE
TM
valve
will keep the Red Flag at the down position, indicating the valve is open and
in operating position.
5) TORREXX vaporizer is now ready to supply vapor. Slowly open the outlet
isolation valve to pressurize the supply piping. Then, fully open the outlet
isolation valve to allow vapor to flow to the load. Heater will cycle
automatically to match the flow conditions.
STOPPING
THE
VAPORIZER
1) Close the outlet isolation valve.
2) Disconnect power.
PURGING
THE
VAPORIZER
Purging procedure should be followed anytime a vaporizer needs to be
maintained, serviced, relocated or shut down for any other reason.
CAUTION
Prior to purging the vaporizer, ensure that there are no closed ball
valves or back check valves restricting the flow of liquid to the tank.
1) Close the valve at the outlet of the vaporizer.
Summary of Contents for TORREXX TX100
Page 8: ......
Page 56: ...APPENDIX A TECHNICAL INFORMATION ...
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 83: ...ASCO Valve used by Algas SDI ...
Page 86: ...ASCO Valve used by Algas SDI ...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......