Installing Power Supplies
7750 SR-12
Page 79
Connect the power cables after the DC PEMs, AC power shelves and rectifiers are installed:
Step 1
Prepare the power cables. See
Preparing the Power Cable on page 69
Step 2
Remove the safety cover from the DC terminal block (
Step 3
Loosen the -VDC and RTN terminal nuts (
).
Step 4
Using the prepared cable(s), connect the RTN positive/return (+) cable to the (RTN)
terminal according to local safety codes.
Step 5
Replace the nuts and tighten with a torque wrench to 56 pound-inches.
Step 6
Connect the VDC cable to the top (-48V) terminal according to local safety codes.
Step 7
Replace the nuts and tighten with a torque wrench to 56 pound-inches.
Step 8
Replace the safety cover (
Figure 25: DC Terminal Block
Step 9
Plug the other end of the AC input power cables into the AC power source.
Step 10
Check the LEDs on each rectifier.
Step 11
Flip the power switch on each DC PEM to the ON position ( | ).
Step 12
Proceed to the next section for instructions to install the SF/CPM(s). Perform the card slot,
card type, MDA, and port preconfigurations prior to installing the IOMs and MDAs. See
Installing the SF/CPM on page 83
for instructions.
VDC
RTN
OFF
O
ON
I
1
2
SR12019
Summary of Contents for 7750 SR-12
Page 1: ...7750 SR 12 INSTALLATION GUIDE Document Part Number 93 0019 01 December 2003 ...
Page 6: ...Page 4 7750 SR 12 Table of Contents ...
Page 14: ...Page 12 7750 SR 12 ...
Page 84: ...Monitoring AC Power Page 82 7750 SR 12 ...
Page 100: ...Establishing Router Connections Page 98 7750 SR 12 ...
Page 150: ...Impeller Trays Page 148 7750 SR 12 ...