3516526A02 Ed. 01
37
Expansion valve
Level 1
Level 2
Description
Values Min. Def. Max.
EEV
u00
Valve type: 1=PWM-type EEV
2=Stepper-type EEV
1
*
2
SH
Superheating set point
K
0.1
8
40
u02
Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A,
12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,
19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A
0
*
24
u03
PWM cycle time
s.
2
6
10
u04
Proportional constant value (P)
1
10 100
u05
Integral constant value (I)
0
10 100
u06
Derivative constant value (D)
0
0
100
u07
Opening value of the electronic expansion valve when cooling is activated
%
u13 50 u12
u08
Duration of valve opening on cooling demand
s.
2
5
240
u09
Valve opening value with sensor error S5 or S6: 0=Fixed opening according to u10;
1=Average opening over the last 24 hours
0
0
1
u10
Valve opening value with sensor error S5 or S6 (if u09=0)
%
u13
0
u12
u11
Manual valve opening value (0=Disabled), (cycles acc. to u03)
(See page 18)
%
u13
0
u12
u12
Maximum valve opening value
%
u13 100 100
u13
Minimum valve opening value
%
0
0
u12
u14
Valve opening value after defrost (0=Disabled), (duration according to u15)
%
0/
u13
0
u12
u15
Duration of valve opening after defrosting
s
0
0
240
u16
Valve opening in case of LOP error (0=valve closed)
%
0/
u13
0
u12
EP
Output to level 1
* According to the set-up wizard.
Summary of Contents for 16526A
Page 43: ...3516526A02 Ed 01 43...