3516526A02 Ed. 01
36
Defrost
Level 1
Level 2
Description
Values Min. Def. Max.
dEF
d0
Defrost frequency (time between 2 starts)
h.
0
6
96
d1
Maximum defrost duration (0=defrost deactivated)
min.
0
*
255
d2
Type of message during the defrost: 0=Sign of the real temperature; 1=Sign of
the temperature at the start of the defrost; 2=Sample of the dEF message
0
2
2
d3
Maximum message duration
(Time added at the end of the defrost process)
min.
0
5
255
d4
Final defrost temperature (by sensor) (If I00
≠
1)
ºC/ºF
0
8.0 50
d5
Defrost on connecting the unit: 0=NO, First defrost according to d0;
1=YES, First defrost according to d6
0
0
1
d6
Delay of the defrost start on connecting the unit
min.
0
0
255
d7
Type of defrost: 0=Resistors; 1=Air / fans; 2=Hot gas
0
*
2
d8
Time calculation between defrost periods:
0=Total real time 1=Sum of COOL time connected
0
0
1
d9
Drip time when a defrost finishes
(Stop COOL and fans)
min.
0
1
255
d30
Defrost strategy in SELFDRIVE mode (See page 25)
0
5
10
d31
Maximum time without defrosting (0=Deactivated)
h.
0
96 999
d32
Maximum time of cold room outside the temperature regulation range
(0=Deactivated)
h.
0
2
10
EP
Output to level 1
Evaporator fans
Level 1
Level 2
Description
Values Min. Def. Max.
FA
n
F0
Fans stop temperature
ºC/ºF. -50 45
50
F1
Sensor 2 differential if fans are stopped
ºC/ºF 0.1 2.0 20.0
F2
Stop fans when the compressor stops 0=No 1=Yes
0
0
1
F3
Status of the fans during the defrost 0=Stopped; 1=Running
0
*
1
F4
Start-up delay after defrost (if F3=0)
Only actuates if higher than d9
min.
0
2
99
EP
Output to level 1
* According to the set-up wizard.