3516526A02 Ed. 01
11
Superheating SET POINT
Enter the desired optimum superheating value.
Assistant
The first time the unit receives the power supply, it will enter into ASSISTANT
mode. The display will show the message
In{
flashing at
0
.
The buttons
and
change the value, the
SET
button accepts the
value and moves on to the next step.
Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press
SET
.
The available options will be shown in the following table:
InI
Type of installation
Parameters
Control of
the compressor
Pump
Down
Defrost
Vent.
Evap.
Pd o00 o20 I00 I10 I11 I20 I21 d1 D7 F3
0
Demo mode: it displays the temperature but does not regulate the temperature
1
No
No
Consumption
Yes
0
0
*
2
0
0
0
0 20 0
0
2
Yes
Yes
Consumption
Yes
1
1
*
2
7
1
0
0 20 0
0
3
Yes
No
Consumption
Yes
0
1
*
2
0
0
0
0 20 0
0
4
No
No
Air
Yes
0
0
*
1
0
0
0
0 20 1
1
5
Yes
Yes
Air
Yes
1
1
*
1
7
1
0
0 20 1
1
6
Yes
No
Air
Yes
0
1
*
1
0
0
0
0 20 1
1
7
Yes
Yes
Hot gas
Yes
1
1
*
2
7
1
7
1
5
2
0
8
Yes
No
Hot gas
Yes
0
1
*
2
0
0
7
1
5
2
0
* If
u00
=2:
o20
=3
If
u00
≠
2:
o20
=0
If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch
type used.
Step 2:
Choose the type of expansion valve to be used:
u00=1
PWM-controlled solenoid valve
u00=2
Electronic expansion valve (Requires an external controller for
the EEV. For more information, please refer to the
available on our website)
If u00=2 is chosen, step 3 is not displayed.
1
/
/ SET
2
/
/ SET
Summary of Contents for 16526A
Page 43: ...3516526A02 Ed 01 43...