background image

3516526A02 Ed. 01

10

Initial configuration

The 

AKO-16526

 controller can be adapted to different types of installation according to the different options chosen 

in the set-up wizard.
Before completing the wiring, make sure you are familiar with the details of the installation in order to configure it 
correctly. 

It is advisable to note the following points:

Compressor

Whether the controller should switch the compressor on and off (InI=  2, 3, 5, 6, 7 or 8) or whether the compressor 
is switched on and off by the low pressure switch (InI=1 or 4).

Defrost

Defrosting method used:
 

Electric (InI= 1, 2 or 3) 

Air (evaporator fans) (InI= 4, 5 or 6)

 

Hot gas valve (Condensing unit) (InI= 7 or 8) 

Solenoid/EEV

Type of solenoid/EEV used:

•  PWM-controlled EEV (without liquid solenoid) (u00= 1)
•  Stepper-controlled EEV (u00= 2). Requires an external controller for the EEV. For more information, please refer 

to the 

application note

 available on our website.

Options u00= 1 and u00=2 require the use of a superheating temperature sensor (S5) and an evaporator pressure 
sensor (S6).

Analogue outputs

The analogue output (ANALOG OUT) enables communication between the controller and the external controller of 
the electronic expansion valve (if u00=2), or with the frequency inverter of the fans (if F10=1), and can be configured 
as 4-20 mA output (o30=0) or as 0-10 V output (o30=1). 
Consult the specifications of the external controller or drive before setting this option.

SET POINT (temperature)

Make a note of the desired set temperature value.

Type of gas

Type of gas used in the installation.

u02=0

R404A

u02=1

R134A

u02=2

R407A

u02=3

R407F

u02=4

R410A

u02=5

R450A

u02=6

R513A

u02=7

R744

u02=8

R449A

u02=9

R290

u02=10

R32

u02=11

R448A

u02=12

R1234ze

u02=13

R23

u02=14

R717

u02=15

R407C

u02=16

1234yf

u02=17

R22

u02=18

R454C

u02=19

R455A

u02=20

R507A

u02=21

R515B

u02=22

R452A

u02=23

R452B

u02=24

R454A

Pressure sensor type

Type of evaporator pressure sensor installed:
 

4-20 mA (I61=1) 

0-5 V (I61=2) 

0.5-4.5 V (I61=3) 

0-10 V (I61=4) 

1-5 V(I61=5)

Note also the maximum and minimum values of the pressure sensor as well as the units of pressure used (bar or Psi).

Summary of Contents for 16526A

Page 1: ...3516526A02 Ed 01 EN AKO 16526A Advanced temperature and electronic expansion controller for cold room store User manual...

Page 2: ...occur due to failure to comply with these regulations Rigorously follow the instructions described in this manual In order to extend the lifetime of our products to the maximum the following points mu...

Page 3: ...be used in a place without heat influences apart from the tem perature you want to measure or control The IP65 protection degree is only valid with the protection cover closed The IP65 protection degr...

Page 4: ...po de v lvula u00 V lvula PWM 1 Regulaci n ventiladores F10 ON OFF 0 Sondas conectadas I00 Temp c mara temp Evap 2 Configuraci n D1 S3 I10 Presostato de baja 7 Configuraci n D3 S5 I30 Temperatura supe...

Page 5: ...The COOL relay is active Flashing The COOL relay should be active but a delay or protection is preventing this Pulsing Expansion valve regulated Constant The SELFDRIVE mode is active Flashing An error...

Page 6: ...to change its value Pressing once without holding activates deactivates the cold room light Pressing it for 3 seconds accesses the condensed programming menu Pressing it for 6 seconds accesses the exp...

Page 7: ...box Mark and make the holes in the wall with the aid of the template included Fix the device to the wall If it is a brick wall use the screws and plugs supplied if the wall is made of sheet metal col...

Page 8: ...a Location of the evaporator probe The probe must be located as near as possible to the inlet of refrigerant from the evaporator close to the expansion valve in the finned area In certain evaporators...

Page 9: ...for relay or contactor outputs should have a section of 2 5 mm2 allow working temperatures equal to or over 70 C and be installed with as little bending as possible The 120 230 V wiring area must be k...

Page 10: ...he use of a superheating temperature sensor S5 and an evaporator pressure sensor S6 Analogue outputs The analogue output ANALOG OUT enables communication between the controller and the external contro...

Page 11: ...plays the temperature but does not regulate the temperature 1 No No Consumption Yes 0 0 2 0 0 0 0 20 0 0 2 Yes Yes Consumption Yes 1 1 2 7 1 0 0 20 0 0 3 Yes No Consumption Yes 0 1 2 0 0 0 0 20 0 0 4...

Page 12: ...A Step 4 Define the pressure units to be used I60 0 Bar I60 1 Psi Step 5 Define the type of pressure sensor used I61 0 Deactivated I61 1 4 20 mA I61 2 0 5 V I61 3 0 5 4 5 V I61 4 0 10 V I61 5 1 5 V St...

Page 13: ...ent the controller stops See page 19 Operation Messages Pump down malfunction error Stop The time configured in parameter C20 has been exceeded See page 19 Only displayed on screen Pump down malfuncti...

Page 14: ...e audible alarm Minimum superheat alarm The value set in A20 has been reached See page 29 Acti vates the alarm relay and the audible alarm Minimum superheat alert The value defined in A23 has been rea...

Page 15: ...ion in 1 2 evaporator There is not enough difference in temperature between the cold room probe and the evaporator probe It has not been possible to carry out the calibration due to a lack of stabilit...

Page 16: ...frost cycles IMPORTANT During the calibration processes the following should be avoided Opening the cold room door Turning the controller off or putting it on stand by Changing controller parameters i...

Page 17: ...olenoid opens causing the pressure in the evaporator to increase and therefore the low pressure switch deactivates and the compressor starts up Once the set point SP value is reached the solenoid clos...

Page 18: ...m line of the display by default Parameter b23 defines which value is displayed on that line When there is no cooling required the superheat value is not updated as the regulation is stopped When the...

Page 19: ...w pressure switch is activated but it will display the Pd message after 15 minutes START When the temperature in sensor S1 reaches the set point value plus the differential SP C1 the COOL relay acti v...

Page 20: ...activating this mode the compressor begins to operate until the temperature in sensor S1 reaches the set point value minus the variation indicated in param eter C10 The value of C10 is always negativ...

Page 21: ...ans of the CAMM module and the AKO CAMM tool application EXAMPLE If the SELFDRIVE mode is active It is recommended for calibration to be performed with the lowest set point value It is recommended tha...

Page 22: ...E operating mode CE 1 If the SELFDRIVE mode is active in the case of opening the door the fans stop or do not stop depending on param eter C22 If the door does not close when the time set in parameter...

Page 23: ...nd solenoid are stopped Hot gas InI 7 and 8 d7 2 The hot gas from compressor discharge is used to melt evaporator ice and to this end two valves are necessary one at the condenser input A and another...

Page 24: ...rost completion Defrost will complete if The temperature programmed in parameter d4 has been reached in sensor 2 This requires a 2nd sensor l00 2 to be available located in the evaporator The time con...

Page 25: ...AIR HOT GAS Fin spacing of the evaporator in mm 3 0 1 2 1 3 4 0 1 2 3 5 0 1 2 1 3 4 0 1 2 4 1 2 3 2 4 5 0 1 2 4 5 2 3 4 3 5 6 1 2 3 5 2 3 5 3 5 7 1 2 3 5 5 2 3 5 3 5 7 1 2 4 6 3 4 6 4 6 8 1 3 4 6 5 3...

Page 26: ...ost I10 or I20 5 Defrost locking This prevents defrost starting at unusual points by means of an external switch which may be useful for ensuring that the installation s load does not excessively incr...

Page 27: ...and F1 sensor differential If sensor S2 is not connected or an error in the sensor E2 is detected the fans continuously operate without taking into account parameters F0 and F1 but taking the remaini...

Page 28: ...deactivate when 10 degrees are reached If A0 1 Absolute the maximum temperature alarm will activate when 10 degrees are reached in sensor 1 and will deactivate when 8 degrees are reached External alar...

Page 29: ...n door alarm is activated In order to detect the open door configuration is required of one of the digital inputs as door contact l10 or l20 1 Activates alarm relay and audible alarm Minimum superheat...

Page 30: ...tion of the maximum operating pressure alarm from when the programmed value is reached Delay to activation of LOP alarm A30 Delays activation of the lowest operating pressure alarm from when the progr...

Page 31: ...r is not in operation it powers the crankcase resistor This function can only be selected via the initial wizard In Light o00 2 This regulates the operation of cold room light See page 31 Virtual cont...

Page 32: ...external control o20 3 Sends the ON OFF signal to the external frequency inverter if F10 1 or to the EVV driver if u00 2 Defrost 2nd Evaporator o20 4 This controls the defrost resistors of a second e...

Page 33: ...m defrost duration 0 defrost deactivated min 0 255 d4 Final defrost temperature by sensor If I00 1 C F 0 8 0 50 SH Superheating set point K 0 1 8 40 F3 Status of the fans during the defrost 0 Stopped...

Page 34: ...enter the password programmed in PAS when attempting to access either of the two functions If the entered password is not correct the unit will go back to showing the temperature IMPORTANT Certain par...

Page 35: ...ays be OFF when disconnected min 0 10 120 C8 Time of relay OFF if sensor 1 damaged If C8 0 and C7 0 the relay will always be ON when connected min 0 5 120 C9 Maximum duration of the continuous cycle m...

Page 36: ...ype of defrost 0 Resistors 1 Air fans 2 Hot gas 0 2 d8 Time calculation between defrost periods 0 Total real time 1 Sum of COOL time connected 0 0 1 d9 Drip time when a defrost finishes Stop COOL and...

Page 37: ...0 u07 Opening value of the electronic expansion valve when cooling is activated u13 50 u12 u08 Duration of valve opening on cooling demand s 2 5 240 u09 Valve opening value with sensor error S5 or S6...

Page 38: ...FF without alarm 1 Relay OFF in alarm ON without alarm 0 0 1 A10 Differential of temperature alarms A1 and A2 C F 0 1 1 0 20 0 A12 Delay of open door alarm if I10 or I20 1 min 0 10 120 A20 Minimum sup...

Page 39: ...room Sensor 2 evaporator 1 2 2 I10 D1 S3 input configuration 0 Deactivated 1 Door contact 2 External alarm 3 Severe external alarm 4 Change SP 5 Remote defrost 6 Defrost lockout 7 Low pressure switch...

Page 40: ...Defrost 2nd evaporator 5 Door frame resistor 6 Drainage resistor 0 0 6 o30 Analogue output type AO 0 4 20mA 1 0 10V 0 0 1 EP Output to level 1 HACCP alarm Level 1 Level 2 Description Values Min Def Ma...

Page 41: ...nt for each unit within the same network The address can be changed using parameter b20 Once modified the old address indicated on the plate will not be valid Tr Tr GND GND Tr Tr RS 485 GND AKO 80039...

Page 42: ...olerance of the NTC probe at 25 C 0 4 C Input for NTC probe AKO 14950 AKO 14950 8 Working ambient temperature 10 C to 50 C Ambient storage temperature 30 C to 60 C Protection degree IP 65 Installation...

Page 43: ...3516526A02 Ed 01 43...

Page 44: ...08812 Sant Pere de Ribes Barcelona Spain Tel 34 902 333 145 Fax 34 938 934 054 www ako com We reserve the right to supply materials slightly different to those described in our Data Sheets Updated inf...

Reviews: