88
Rev 2.1
Configure
→
System Configuration
→
Temperature Units
Textbox (Default: Fahrenheit)
•
Select
Fahrenheit
to show temperature in Fahrenheit
•
Select
Celsius
to show temperature in Celsius
This parameter determines whether temperature is represented in units of Fahrenheit or Celsius degrees.
5-24.7 To Turn On And Off The Unit Using Burner Switch
Operation
→
Burner Switch
Button (Default: Yes/True/On)
This parameter enables or disables the burner control. When it is off, the burner will not fire.
5-24.8 To Enable Pump Test
Diagnostics
→
Diagnostics
Test
→
Pump Test
Button
Enables the installer to verify that the correct pump contacts are on or off. The Start Test button will test all pump
contacts; pressing an individual pump tests that pump contact only.
5-24.9 To Enable Modulation Test
Diagnostics
→
Diagnostics
Test
→
Modulation Test
Button
Enables the user to verify that the unit is firing at the correct rate.
5-24.10 To Enable Pilot Test
Diagnostics
→
Diagnostics
Test
→
Pilot Test
Button
Enables the user to verify that the pilot valve is functioning properly. The installer can also perform adjustments for the
pilot flame.
Summary of Contents for A050-A300
Page 28: ...28 Rev 2 1 ...
Page 31: ...31 Rev 2 1 Figure 2 10 One Atlas One Tank Suggest Piping Diagram ...
Page 32: ...32 Rev 2 1 Figure 2 11 One Atlas Two Tank Piping Diagram ...
Page 33: ...33 Rev 2 1 Figure 2 12 Two Atlas One Tank Piping Diagram ...
Page 34: ...34 Rev 2 1 Figure 2 13 Two Atlas Two Tank Piping Diagram ...
Page 36: ...36 Rev 2 1 Figure 2 15 Two Atlas in Primary Secondary Loop Piping Diagram ...
Page 113: ...113 Rev 2 1 ...