74
Rev 2.1
5-3.10 To Change DHW Loop P-I-D Parameters
Configure
→
DHW – Domestic Hot Water Configuration
→
P-Gain
Textbox (Default: 50)
Configure
→
DHW – Domestic Hot Water Configuration
→
I-Gain
Textbox (Default: 50)
Configure
→
DHW – Domestic Hot Water Configuration
→
D-Gain
Textbox (Default: 0)
•
Type in desired number between 0 to 400
P gain applied to the proportional term of the PID equation for the DHW loop.
I gain applied to the Integral term of the PID equation for the DHW loop.
D gain applied to the Differential term of the PID equation for the DHW loop.
5-3.11 To Change DHW Modulation Sensor
Configure
→
DHW – Domestic Hot Water Configuration
→
Modulation Sensor
Textbox
(DHW Mode Default: DHW Sensor, Com Mode Default: Outlet Sensor (S1))
•
Select
DHW sensor
for DHW modulation sensor
•
Select
Outlet sensor
for DHW modulation sensor
•
Select
Inlet sensor
for DHW modulation sensor
•
Select
Auto DHW (S6) of Inlet (S1)
for Inlet modulation sensor when DHW switch is enabled
•
Select
Auto DHW (S6) of Outlet (S1)
for outlet modulation sensor when DHW switch is enabled
5-3.12 To Change DHW Loop Priority Versus LL
Configure
→
DHW – Domestic Hot Water Configuration
→
DHW Priority vs Lead Lag
Textbox (Default: DHW>LL)
•
Select
LL>DHW
for no priority over LL loop
•
Select
DHW>LL
for priority over LL loop
This parameters determines the priority of DHW vs. the LL call-for heat, when both of these are enabled and active. (If
DHW has a lower priority, it may be boosted to the highest priority temporarily via the DHW Priority Time parameter.)
5-4 Modulation Related Configuration
5-4.1 To Change CH Loop Maximum Modulation Rate
Configure
→
Modulation Configuration
→
CH Maximum Modulation Rate
Textbox
(Default: Varies based on model)
•
Type in RPM rate between light off rate and maximum modulation rate
Provides the upper limit of modulation when firing for CH or LL slave mode.
5-4.2 To Change DHW Loop Maximum Modulation Rate
Configure
→
Modulation Configuration
→
DHW Maximum Modulation Rate
Textbox
(Default: Varies based on model)
•
Type in RPM rate between light off rate and maximum modulation rate
Provides the upper limit of modulation when firing for DHW.
5-4.3 To Change CH Loop Forced Rate Time
Configure
→
Modulation Configuration
→
CH Forced Rate Time
Textbox (Default: 0m10s)
•
Type in desired time between 0 to 5 minutes
For CH demand, if the CH forced rate time is non-zero, then the firing rate will be held at the rate specified here during
that time. This parameter is also needed as the starting point for Slow State, even if the forced rate time is zero.
5-4.4 To Change CH Loop Forced Rate
Configure
→
Modulation Configuration
→
CH Forced Rate
Textbox (Default: Varies based on model)
•
Type in RPM rate between light off rate and maximum modulation rate
For CH demand, if this time is non-zero then, upon entry to Run, the firing rate will be held at the CH forced rate.
Summary of Contents for A050-A300
Page 28: ...28 Rev 2 1 ...
Page 31: ...31 Rev 2 1 Figure 2 10 One Atlas One Tank Suggest Piping Diagram ...
Page 32: ...32 Rev 2 1 Figure 2 11 One Atlas Two Tank Piping Diagram ...
Page 33: ...33 Rev 2 1 Figure 2 12 Two Atlas One Tank Piping Diagram ...
Page 34: ...34 Rev 2 1 Figure 2 13 Two Atlas Two Tank Piping Diagram ...
Page 36: ...36 Rev 2 1 Figure 2 15 Two Atlas in Primary Secondary Loop Piping Diagram ...
Page 113: ...113 Rev 2 1 ...