Extended the exhaust pipe according to the following procedure by referring to the figure below.
1. Remove the exhaust top from the outdoor unit exhaust port.
2. Connect the extra sections sequentially from the outdoor unit side, and extend the exhaust pipe to the
desired position following the restriction below.
• Total length of the exhaust pipe extension shall not exceed 15 m.
• Total number of exhaust pipe bends (bending angle = 90 °) shall not exceed 5 (each equivalent
length 1m).
• The extended pipe shall be anchored to the building or similar structure with fixing brackets every
1.5 to 2 m.
• The exhaust pipe shall not be gathered or connected with the other exhaust pipe.
2. Attach the exhaust top at th outlet of the extended exhaust pipe paying attention to the following:
• The angle of the exhaust vent plane shall be vertical to the ground by adjusting the elbow pipes so
that rainwater may not enter the exhaust pipe directly.
• Apply silicone caulking material at the lower part of the metal mesh in accordance with the following
figure so that the drain water may not drip from the exhaust top. (Refer to the figure below.)
Summary of Contents for AXGP224E1
Page 1: ......
Page 2: ...2 ...
Page 4: ...4 ...
Page 7: ...7 1 2 External dimensions ...
Page 25: ...25 1 12 2 Wiring example AC 230 V single phase ...
Page 26: ...26 1 13 Power supply wiring procedure 1 13 1 Wiring instruction ...
Page 32: ...32 2 2 External dimensions ...
Page 40: ...40 2 7 Outline diagram of refrigerant piping 2 7 1 Combined installation ...
Page 41: ...41 2 7 2 Stand alone installation ...
Page 59: ...59 2 13 Power supply wiring procedure 2 13 1 Wiring instruction combined installation ...
Page 60: ...60 2 13 2 Wiring instruction stand alone installation ...
Page 62: ...62 2 14 2 Wiring example AC 230V single phase ...
Page 85: ...19 11 4 HVAC installation layout AWS E1 ...
Page 86: ...20 11 5 HVAC installation E1 with proportional distribution of consumption ...
Page 87: ...21 11 6 HVAC installation AWS E1J variable flow rate no hydraulic separator AHU ...
Page 88: ...22 11 7 HVAC installation AWS E1J variable flow rate with hydraulic separator fan coil ...
Page 93: ...27 NOTE ...
Page 94: ...28 ...
Page 95: ...29 ...
Page 96: ......
Page 109: ...13 7 2 Detailed wiring diagram ...
Page 115: ...19 11 4 HVAC installation AWS E1J TWIN ...
Page 116: ...20 11 5 HVAC installation E1J TWIN proportional distribution of consumption ...
Page 117: ...21 11 6 HVAC installation AWS E1J TWIN variable flow rate no hydraulic separator AHU ...
Page 118: ...22 11 7 HVAC installation AWS E1J TWIN variable flow rate with hydraulic separator fan coil ...
Page 123: ...27 NOTE ...
Page 124: ...28 ...
Page 125: ......
Page 126: ......