Example modulation in cooling:
The set point temperature in cooling, ie the parameter "Tset cool", may vary in a range between
6°C and 15°C.
The factory settings are:
Tset cool= 8°C;
Modulation Range = 5°C
AWS Capacity
[%]
Tset cool [°C]
Modulation
Range [°C]
Max. Temperature
Modulation [°C]
Outlet
Temperature [°C]
100
A
∆
T
A +
∆
T
A - 1
75
(A +
∆
T) - (
∆
T•0,25)
50
(A +
∆
T) - (
∆
T • 0,5)
25
(A +
∆
T) - (
∆
T•0,75)
Numerical example on the minimum temperature set point
100
6
5
11
5
75
9,75
50
8,5
25
7,25
Numerical example on the maximum temperature set point
100
15
7
22
14
75
20,25
50
18,5
25
16,75
The YOHSI AWS TWIN unit proper operation foresees the following capacity modulation method of
the two GHP units:
■
Two GHP units at 100% of their load;
■
Two GHP units at 75% of their load;
■
Two GHP units at 50% of their load;
■
One GHP unit at 50% of its load;
■
One GHP unit at 25 % of its load.
10.2 Setting the offset
The unit YOSHI AWS allows you to adjust the offset of the set point temperature, that is the return
water temperature on the primary circuit. The parameters "Tset Offset " can be changed in the user
menu, (please refer to the AWS service manual). If the optional "Controller Plus" has been installed,
of the offset measurement will be made by its active probe, installed on the buffer tank.
The factory settings are:
Heat Tset Offset = 2°C
Cool Tset Offset = 2°C
Summary of Contents for AXGP224E1
Page 1: ......
Page 2: ...2 ...
Page 4: ...4 ...
Page 7: ...7 1 2 External dimensions ...
Page 25: ...25 1 12 2 Wiring example AC 230 V single phase ...
Page 26: ...26 1 13 Power supply wiring procedure 1 13 1 Wiring instruction ...
Page 32: ...32 2 2 External dimensions ...
Page 40: ...40 2 7 Outline diagram of refrigerant piping 2 7 1 Combined installation ...
Page 41: ...41 2 7 2 Stand alone installation ...
Page 59: ...59 2 13 Power supply wiring procedure 2 13 1 Wiring instruction combined installation ...
Page 60: ...60 2 13 2 Wiring instruction stand alone installation ...
Page 62: ...62 2 14 2 Wiring example AC 230V single phase ...
Page 85: ...19 11 4 HVAC installation layout AWS E1 ...
Page 86: ...20 11 5 HVAC installation E1 with proportional distribution of consumption ...
Page 87: ...21 11 6 HVAC installation AWS E1J variable flow rate no hydraulic separator AHU ...
Page 88: ...22 11 7 HVAC installation AWS E1J variable flow rate with hydraulic separator fan coil ...
Page 93: ...27 NOTE ...
Page 94: ...28 ...
Page 95: ...29 ...
Page 96: ......
Page 109: ...13 7 2 Detailed wiring diagram ...
Page 115: ...19 11 4 HVAC installation AWS E1J TWIN ...
Page 116: ...20 11 5 HVAC installation E1J TWIN proportional distribution of consumption ...
Page 117: ...21 11 6 HVAC installation AWS E1J TWIN variable flow rate no hydraulic separator AHU ...
Page 118: ...22 11 7 HVAC installation AWS E1J TWIN variable flow rate with hydraulic separator fan coil ...
Page 123: ...27 NOTE ...
Page 124: ...28 ...
Page 125: ......
Page 126: ......