Page 85
Test cap
CLOSED
O
PE
N
CL
OS
ED
OPEN
Stow tube
2. Turn on the unit in COOLING mode. You will hear
the drain pump.Check whether the water is discharged
properly (a 1-minute lag is possible, depending on the
length of the drain pipe), Check whether water leaks from
the joints.
3. Turn off the air conditioner and put the cap back on.
• After turn off the air conditioner 3 minutes, check
whether there is anything abnormal. If drainage
pipes have not been distributed properly, over
back-flow water shall cause the flashing of alarm
indicator at remote-controlled receiving board and
even water shall run over the water collector.
• Continuously infusing water until water level
alarmed, check whether the drainage pump could
discharge water at once. If water level does not
decline under warning water level 3 minutes
later, it shall cause shutdown of unit. When this
situation happens, the normal startup only can
be recovered by turning down power supply and
eliminating accumulated water.
Note: Drain plug at the main water-containing plate
is used for eliminating accumulated water in water-
containing plate when maintaining air conditioner fault.
During normal operation, the plug shall be filled in to
prevent leakage.
5.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering
parts.
Installation
Summary of Contents for YFAD-100R-01M25
Page 15: ...Page 15 4 Centre of gravity 18K 24K...
Page 16: ...Page 16 36K...
Page 17: ...Page 17 48K 60K...
Page 19: ...Page 19 DFMD 100N 01M25...
Page 20: ...DFMD 100N 01T35 Page 20...
Page 22: ...DFMD 160N 01M25 Page 22...
Page 27: ...Page 27 YFAD 100R 01M25...
Page 28: ...YFAD 100R 01T35 Page 28...
Page 29: ...Page 29 YFAD 140R 01T35...
Page 30: ...YFAD 160R 01T35 Page 30...
Page 56: ...Page 56 11 Static Pressure 18K 24K...
Page 57: ...Page 57 30K 36K 48K 60K...
Page 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...