Page 52
Model
60K
Pipe Length (m)
Cooling
5
10
20
30
40
50
Height
difference
H (m)
Indoor
Upper
than
Outdoor
30
0.772
0.698
0.625
20
0.858
0.784
0.709
0.634
10
0.947
0.871
0.796
0.720
0.644
5
0.995
0.957
0.880
0.804
0.727
0.650
0
1.000
0.962
0.885
0.808
0.731
0.654
Outdoor
Upper
than
Indoor
-5
1.000
0.962
0.885
0.808
0.731
0.654
-10
0.962
0.885
0.808
0.731
0.654
-20
0.885
0.808
0.731
0.654
-30
0.808
0.731
0.654
Heating
5
10
20
30
40
50
Height
difference
H (m)
Indoor
Upper
than
Outdoor
30
0.909
0.872
0.836
20
0.945
0.909
0.872
0.836
10
0.982
0.945
0.909
0.872
0.836
5
1.000
0.982
0.945
0.909
0.872
0.836
0
1.000
0.982
0.945
0.909
0.872
0.836
Outdoor
Upper
than
Indoor
-5
0.992
0.974
0.938
0.902
0.865
0.829
-10
0.966
0.930
0.894
0.858
0.823
-20
0.923
0.887
0.852
0.816
-30
0.880
0.845
0.810
Summary of Contents for YFAD-100R-01M25
Page 15: ...Page 15 4 Centre of gravity 18K 24K...
Page 16: ...Page 16 36K...
Page 17: ...Page 17 48K 60K...
Page 19: ...Page 19 DFMD 100N 01M25...
Page 20: ...DFMD 100N 01T35 Page 20...
Page 22: ...DFMD 160N 01M25 Page 22...
Page 27: ...Page 27 YFAD 100R 01M25...
Page 28: ...YFAD 100R 01T35 Page 28...
Page 29: ...Page 29 YFAD 140R 01T35...
Page 30: ...YFAD 160R 01T35 Page 30...
Page 56: ...Page 56 11 Static Pressure 18K 24K...
Page 57: ...Page 57 30K 36K 48K 60K...
Page 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...