Page 80
5. Refer to the following static pressure guidelines when
installing the indoor unit.
Model(KBtu/h)
Static Pressure(Pa)
18~24
0-80
30~36
0-100
48~60
0-160
Change the fan motor static pressure according to external
duct static pressure.
NOTE: 1. Do not put the connecting duct weight on the
indoor unit.
2. When connecting the duct, use an nonflammable
canvas tie-in to prevent vibrating.
3. When connecting duct, install in place prone to
takedown for maintenance.
4. Change the fan motor static pressure corresponding to
external duct static pressure.
5. If installed in place like meeting room where noise is
easy to be perceived, design isolation booth and internal
duct underlayer to muffle the duct system and weaken the
air encounter noise in the duct.
Adjust the air inlet direction(From rear side
to under-side.)
1.
Take off ventilation panel and flange,
Air return flange
Ventilation panel
Bend the rear ventilation panel 90 degrees along the
dotted line into a descending ventilation panel.(some
models)
2. Change the mounting positions of ventilation panel and
air return flange .
Air return flange
Ventilation panel
3. When installing the filter mesh, fit it into the flange as
illustrated in the following figure.
Or
Air return flange
Ventilation panel
NOTE: All the figures in this manual are for demonstration
purposes only. The air conditioner you have purchased may
be slightly different in design, though similar in shape.
3.5 Fresh air duct installation
Dimension :
Duct joint for fresh air
9-12k
Ø92mm(3.62”)
Ø113mm(4.45”)
Installation
Summary of Contents for YFAD-100R-01M25
Page 15: ...Page 15 4 Centre of gravity 18K 24K...
Page 16: ...Page 16 36K...
Page 17: ...Page 17 48K 60K...
Page 19: ...Page 19 DFMD 100N 01M25...
Page 20: ...DFMD 100N 01T35 Page 20...
Page 22: ...DFMD 160N 01M25 Page 22...
Page 27: ...Page 27 YFAD 100R 01M25...
Page 28: ...YFAD 100R 01T35 Page 28...
Page 29: ...Page 29 YFAD 140R 01T35...
Page 30: ...YFAD 160R 01T35 Page 30...
Page 56: ...Page 56 11 Static Pressure 18K 24K...
Page 57: ...Page 57 30K 36K 48K 60K...
Page 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...