Page 50
Model
36K
Pipe Length (m)
Cooling
5
10
15
20
25
30
Height
difference
H (m)
Indoor
Upper
than
Outdoor
20
0.820
0.775
0.729
15
0.878
0.832
0.786
0.740
10
0.938
0.892
0.845
0.798
0.752
5
0.995
0.948
0.901
0.854
0.806
0.759
0
1.000
0.953
0.905
0.858
0.810
0.763
Outdoor
Upper
than
Indoor
-5
1.000
0.953
0.905
0.858
0.810
0.763
-10
0.953
0.905
0.858
0.810
0.763
-15
0.905
0.858
0.810
0.763
-20
0.858
0.810
0.763
Heating
5
10
15
20
25
30
Height
difference
H (m)
Indoor
Upper
than
Outdoor
20
0.935
0.914
0.892
15
0.957
0.935
0.914
0.892
10
0.978
0.957
0.935
0.914
0.892
5
1.000
0.978
0.957
0.935
0.914
0.892
0
1.000
0.978
0.957
0.935
0.914
0.892
Outdoor
Upper
than
Indoor
-5
0.992
0.971
0.949
0.928
0.906
0.885
-10
0.963
0.942
0.920
0.899
0.878
-15
0.934
0.913
0.892
0.871
-20
0.906
0.885
0.864
Summary of Contents for YFAD-100R-01M25
Page 15: ...Page 15 4 Centre of gravity 18K 24K...
Page 16: ...Page 16 36K...
Page 17: ...Page 17 48K 60K...
Page 19: ...Page 19 DFMD 100N 01M25...
Page 20: ...DFMD 100N 01T35 Page 20...
Page 22: ...DFMD 160N 01M25 Page 22...
Page 27: ...Page 27 YFAD 100R 01M25...
Page 28: ...YFAD 100R 01T35 Page 28...
Page 29: ...Page 29 YFAD 140R 01T35...
Page 30: ...YFAD 160R 01T35 Page 30...
Page 56: ...Page 56 11 Static Pressure 18K 24K...
Page 57: ...Page 57 30K 36K 48K 60K...
Page 93: ...Page 93 Design Static Pressure 3 Dynamic Losses For dynamic losses please refer to below image...