Page 48
8. Capacity Correction Factor for Height Difference
8.1 Heat pump models
Model
18K
Pipe Length (m)
Cooling
5
10
15
25
Height
difference
H (m)
Indoor
Upper
than
Outdoor
15
0.915
0.861
10
0.957
0.929
0.874
5
0.995
0.967
0.939
0.883
0
1.000
0.972
0.944
0.887
Outdoor
Upper
than
Indoor
-5
1.000
0.972
0.944
0.887
-10
0.972
0.944
0.887
-15
0.944
0.887
Heating
5
10
15
25
Height
difference
H (m)
Indoor
Upper
than
Outdoor
15
0.977
0.953
10
0.988
0.977
0.953
5
1.000
0.988
0.977
0.953
0
1.000
0.988
0.977
0.953
Outdoor
Upper
than
Indoor
-5
0.992
0.980
0.969
0.945
-10
0.973
0.961
0.938
-15
0.953
0.930