Pr
oduct Featur
es
Page 100
• If the following conditions are satisfied, the
compressor ceases operation.
• While calculated frequency(fb) is less than minimum
limit frequency(FminC).
• While protective time is more than or equal to ten
minutes.
• While T1 is lower than or equal to (Tsc-CDIFTEMP-
0.5°C)
2) When the compressor runs continuously for more than
120 minutes.
• If the following conditions are satisfied, the
compressor ceases operation.
• When calculated frequency(fb) is less than minimum
limit frequency(FminC).
• When protective time is more than or equal to ten
minutes.
• When T1 is lower than or equal to (Tsc-CDIFTEMP).
3) If one of the following conditions is satisfied, not judge
protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is more than 15°C or T4 fault.
• Change setting temperature.
• Turbo or sleep function on/off
• Various frequency limit shutdown occurs.
1.5.2 Indoor Fan Control
1) In cooling mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%, or low,
medium, high and auto.
2) Auto fan action in cooling mode:
• Descent curve
• When T1-Tsc is lower than or equal to 3.5°C, fan
speed reduces to 80%;
• -When T1-Tsc is lower than or equal to 1°C, fan
speed reduces to 60%;
• -When T1-Tsc is lower than or equal to 0.5°C, fan
speed reduces to 40%;
• -When T1-Tsc is lower than or equal to 0°C, fan
speed reduces to 20%;
• -When T1-Tsc is lower than or equal to -0.5°C, fan
speed reduces to 1%.
• Rise curve
• When T1-Tsc is higher than 0°C, fan speed
increases to 20%;
• -When T1-Tsc is higher than 0.5°C, fan speed
increases to 40%;
• -When T1-Tsc is higher than 1°C, fan speed
increases to 60%;
• -When T1-Tsc is higher than 1.5°C, fan speed
increases to 80%;
• -When T1-Tsc is higher than 4°C, fan speed
increases to 100%.
1.5.3 Outdoor Fan Control
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
1.5.4 Condenser Temperature Protection
When the condenser temperature exceeds a configured
value, the compressor ceases operation.
1.5.5 Evaporator Temperature Protection
• Off: Compressor stops.
• Decrease: Decrease the running frequency to the lower
level per 1 minute.
• Hold: Keep the current frequency.
• Resume: No limitation for frequency.
1.6 Heating Mode(Heat Pump Units)
1.6.1 Compressor Control
Summary of Contents for YDAX-035H-09M25
Page 11: ...Page 11 3 Dimensional Drawings Indoor Unit Compact Cassette...
Page 13: ...Page 13 Outdoor Unit YDAX 035H 09M25...
Page 14: ...Page 14 YDAX 050H 09M25...
Page 15: ...Page 15 YDAX 070H 09M25...
Page 16: ...Page 16 YDAX 100H 09M25 YDAX 100H 09T35 YDAX 140H 09T35...
Page 17: ...Page 17 YDAX 140H 09T35...
Page 19: ...Page 19 12K 18K 24K 55K...
Page 27: ...Page 27 YDAX 035H 09M25 YDAX 050H 09M25...
Page 28: ...Page 28 YDAX 070H 09M25...
Page 29: ...Page 29 YDAX 100H 09M25...
Page 30: ...Page 30 YDAX 100H 09T35 YDAX 140H 09T35...
Page 92: ...Specifications Page 92 12k 18k 24k 30k...
Page 93: ...Specifications Page 93 36k 42k 48k 55k...
Page 95: ...Page 95 YDAX 070H 09M25 YDAX 100H 09M25 YDAX 100H 09T35...
Page 96: ...Page 96 YDAX 140H 09T35...
Page 105: ...Product Features Page 105 Remote LCD Screen Indicators...