Installation
Page 134
For Vertical drainage pipe
(The following table is for
reference)
PVC
pipe
Reference
value of inner
diameter of
pipe (mm)
Allowable
maximum water
flowrate (l/h)
Remark
PVC25
20
220
For branch
pipe
PVC32
25
410
PVC40
31
730
Could be
used for
confluence
pipe
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main
pipe.
3. Individual design of drainage pipe system
•
The drainage pipe of air conditioner shall be in-
stalled separately with other sewage pipe, rainwater
pipe and drainage pipe in building.
•
The drainage pipe of the indoor unit with water
pump should be apart from the one without water
pump.
4. Supporter gap of drainage pipe
•
In general, the supporter gap of the drainage pipe
horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
•
Each vertical pipe shall be equipped with not less
than two hangers.
•
Overlarge hanger gap for horizontal pipe shall cre-
ate bending, thus leading to air block.
5. The horizontal pipe layout should avoid converse flow or
bad flow
•
The correct installation will not cause converse
water flow and the slope of the branch pipes can be
adjusted freely
•
The false installation will cause converse water flow
and the slope of the branch pipe can not be ad-
justed.
6. Water storage pipe setting
•
If the indoor unit has high extra static pressure and
without water pump to elevate the condensate wa-
ter, such as high extra static pressure duct unit , the
water storage pipe should be set to avoid converse
flow or blow water phenomena.
7. Lifting pipe setting of indoor unit with water pump
•
The length of lifting pipe should not exceed
750mm/29.5in.
•
The drainage pipe should be set down inclined after
the lifting pipe immediately to avoid wrong opera-
tion of water level switch.
•
Refer the following picture for installation reference.
8. Blowhole setting
•
For the concentrated drainage pipe system, there
should design a blowhole at the highest point of
main pipe to ensure the condensate water discharge
smoothly.
•
The air outlet shall face down to prevent dirt enter-
Summary of Contents for YDAX-035H-09M25
Page 11: ...Page 11 3 Dimensional Drawings Indoor Unit Compact Cassette...
Page 13: ...Page 13 Outdoor Unit YDAX 035H 09M25...
Page 14: ...Page 14 YDAX 050H 09M25...
Page 15: ...Page 15 YDAX 070H 09M25...
Page 16: ...Page 16 YDAX 100H 09M25 YDAX 100H 09T35 YDAX 140H 09T35...
Page 17: ...Page 17 YDAX 140H 09T35...
Page 19: ...Page 19 12K 18K 24K 55K...
Page 27: ...Page 27 YDAX 035H 09M25 YDAX 050H 09M25...
Page 28: ...Page 28 YDAX 070H 09M25...
Page 29: ...Page 29 YDAX 100H 09M25...
Page 30: ...Page 30 YDAX 100H 09T35 YDAX 140H 09T35...
Page 92: ...Specifications Page 92 12k 18k 24k 30k...
Page 93: ...Specifications Page 93 36k 42k 48k 55k...
Page 95: ...Page 95 YDAX 070H 09M25 YDAX 100H 09M25 YDAX 100H 09T35...
Page 96: ...Page 96 YDAX 140H 09T35...
Page 105: ...Product Features Page 105 Remote LCD Screen Indicators...