1. Operation Modes and Functions
1.1 Abbreviation
Unit element abbreviations
Abbreviation
Element
T1
Indoor room temperature
T2
Coil temperature of evaporator
T3
Coil temperature of condenser
T4
Outdoor ambient temperature
TP
Compressor discharge temperature
Tsc
Adjusted setting temperature
In this manual, such as CDIFTEMP, HDIFTEMP2, TCE1,
TCE2...etc., they are well-setting parameter of EEPROM.
1.2 Safety Features
Compressor three-minute delay at restart
Compressor functions are delayed for up to ten seconds
upon the first startup of the unit, and are delayed for up
to three minutes upon subsequent unit restarts.
Automatic shutoff based on discharge temperature
If the compressor discharge temperature exceeds a certain
level for nine seconds, the compressor ceases operation.
Automatic shutoff based on fan speed
If the indoor fan speed registers below 200RPM or over
2100RPM for an extended period of time, the unit ceases
operation
Inverter module protection
The inverter module has an automatic shutoff mechanism
based on the unit’s current, voltage, and temperature.
If automatic shutoff is initiated, the corresponding error
code is displayed on the indoor unit and the unit ceases
operation.
Indoor fan delayed operation
• When the unit starts, the louver is automatically
activated and the indoor fan will operate after a
period of setting time or the louver is in place.
• If the unit is in heating mode, the indoor fan is
regulated by the anti-cold wind function.
Compressor preheating
Preheating is automatically activated when T4 sensor is
lower than setting temperature.
Sensor redundancy and automatic shutoff
• If one temperature sensor malfunctions, the air
conditioner continues operation and displays the
corresponding error code, allowing for emergency use.
• When more than one temperature sensor is
malfunctioning, the air conditioner ceases operation.
1.3 Display Function
Unit display functions
Compact Cassette
Super-slim Cassette
Operation
indicator
Electric heating
indicator
( some models)
Timer
indicator
PRE-DEF indicator
(pre-heating/defrost)
Alarm indicator
When wireless control
feature is activated
( some models)
LED display
1.4 Fan Mode
When fan mode is activated:
• The outdoor fan and compressor are stopped.
• Temperature control is disabled and no temperature
setting is displayed.
• The indoor fan speed can be set to 1%~100%, or low,
medium, high and auto.
• The louver operations are identical to those in cooling
mode.
• Auto fan: In fan-only mode, AC operates the same as
auto fan in cooling mode with the temperature set at
24°C.
1.5 Cooling Mode
1.5.1 Compressor Control
Reach the configured temperature:
1) When the compressor runs continuously for less than
120 minutes.
Summary of Contents for YDAX-035H-09M25
Page 11: ...Page 11 3 Dimensional Drawings Indoor Unit Compact Cassette...
Page 13: ...Page 13 Outdoor Unit YDAX 035H 09M25...
Page 14: ...Page 14 YDAX 050H 09M25...
Page 15: ...Page 15 YDAX 070H 09M25...
Page 16: ...Page 16 YDAX 100H 09M25 YDAX 100H 09T35 YDAX 140H 09T35...
Page 17: ...Page 17 YDAX 140H 09T35...
Page 19: ...Page 19 12K 18K 24K 55K...
Page 27: ...Page 27 YDAX 035H 09M25 YDAX 050H 09M25...
Page 28: ...Page 28 YDAX 070H 09M25...
Page 29: ...Page 29 YDAX 100H 09M25...
Page 30: ...Page 30 YDAX 100H 09T35 YDAX 140H 09T35...
Page 92: ...Specifications Page 92 12k 18k 24k 30k...
Page 93: ...Specifications Page 93 36k 42k 48k 55k...
Page 95: ...Page 95 YDAX 070H 09M25 YDAX 100H 09M25 YDAX 100H 09T35...
Page 96: ...Page 96 YDAX 140H 09T35...
Page 105: ...Product Features Page 105 Remote LCD Screen Indicators...