Installation
Page 137
7. Vacuum Drying and Leakage
Checking
7.1 Purpose of vacuum drying
•
Eliminating moisture in system to prevent the phe-
nomena of ice-blockage and copper oxidation
.
Ice-blockage shall cause abnormal operation of
system, while copper oxide shall damage
compressor.
•
Eliminating the non-condensable gas (air) in system
to prevent the components oxidizing, pressure fluc-
tuation and bad heat exchange during the operation
of system.
7.2 Selection of vacuum pump
•
The ultimate vacuum degree of vacuum pump shall
be -756mmHg or above.
•
Precision of vacuum pump shall reach 0.02mmHg or
above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of
vacuum drying ways could be chosen, namely ordinary
vacuum drying and special vacuum drying.
7.3.1
Ordinary vacuum drying
1. When conduct first vacuum drying, connect pressure
gauge to the infusing mouth of gas pipe and liquid pipe,
and keep vacuum pump running for 1hour (vacuum
degree of vacuum pump shall be reached -755mmHg).
2. If the vacuum degree of vacuum pump could not reach
-755mmHg after 1 hour of drying, it indicates that there is
moisture or leakage in pipeline system and need to go on
with drying for half an hour.
3. If the vacuum degree of vacuum pump still could not
reach -755mmHg after 1.5 hours of drying, check whether
there is leakage source.
4 . Leakage test: After the vacuum degree reaches
-755mmHg, stop vacuum drying and keep the pressure for
1 hour. If the indicator of vacuum gauge does not go up,
it is qualified. If going up, it indicates that there is moisture
or leak source.
7.3.2
Special vacuum drying
The special vacuum drying method shall be adopted when:
1. Finding moisture during flushing refrigerant pipe.
2. Conducting construction on rainy day, because rain
water might penetrated into pipeline.
3. Construction period is long, and rain water might
penetrated into pipeline.
4. Rain water might penetrate into pipeline during
construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could
achieve the effect of vacuum drying, but this method
could not achieve drying thoroughly when there is too
much moisture. Therefore, special attention shall be drawn
to prevent the entering of water and the formation of
condensate water.
3. Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure
leakage test. If it cannot reached the value, repeat vacuum
damage and vacuum drying again for 1 hour.
4. Leakage test: After the vacuum degree reaches
-755mmHg, stop vacuum drying and keep the pressure for
1 hour. If the indicator of vacuum gauge does not go up,
it is qualified. If going up, it indicates that there is moisture
or leak source.
Summary of Contents for YDAX-035H-09M25
Page 11: ...Page 11 3 Dimensional Drawings Indoor Unit Compact Cassette...
Page 13: ...Page 13 Outdoor Unit YDAX 035H 09M25...
Page 14: ...Page 14 YDAX 050H 09M25...
Page 15: ...Page 15 YDAX 070H 09M25...
Page 16: ...Page 16 YDAX 100H 09M25 YDAX 100H 09T35 YDAX 140H 09T35...
Page 17: ...Page 17 YDAX 140H 09T35...
Page 19: ...Page 19 12K 18K 24K 55K...
Page 27: ...Page 27 YDAX 035H 09M25 YDAX 050H 09M25...
Page 28: ...Page 28 YDAX 070H 09M25...
Page 29: ...Page 29 YDAX 100H 09M25...
Page 30: ...Page 30 YDAX 100H 09T35 YDAX 140H 09T35...
Page 92: ...Specifications Page 92 12k 18k 24k 30k...
Page 93: ...Specifications Page 93 36k 42k 48k 55k...
Page 95: ...Page 95 YDAX 070H 09M25 YDAX 100H 09M25 YDAX 100H 09T35...
Page 96: ...Page 96 YDAX 140H 09T35...
Page 105: ...Product Features Page 105 Remote LCD Screen Indicators...