Electric wiring and the application
6. Parameters of phase order detect (Local):
SW9 SW10 SW11
Function
Operational approach
11
0
0
Times of ok for phase S
(
20 times as normal,
alarm 37-1 when lower than 16 times
)
11
1-10
0
Observe the time of low level for phase S 10ms
Unit
:
0.1ms
11
0
1
Times of ok for phase S
(
20 times as normal,
alarm 37-1 when lower than 16 times
)
11
1-10
1
Observe the period of phase S 20ms
Unit
:
0.1ms
11
0
2
Times of ok for phase T
(
20 times as normal,
alarm 37-2 when lower than 16 times
)
11
1-10
2
Observe the time of low level for phase T 10ms
Unit
:
0.1ms
11
0
3
Times of ok for phase T
(
20 times as normal,
alarm 37-2 when lower than 16 times
)
11
1-10
3
Observe the period of phase T 20ms
Unit
:
0.1ms
11
0
4
Times of ok for phase S/T order T
(
10 times as
normal, alarm 37-3 when lower than 7 times
)
7. Examination of local ee data:
SW9 SW10 SW11
Function
Display with digital tube LED1
~
4
12
0
0
The EE data of address 000H
(
Version E2
)
The first 256 bytes data display of local
EE
(
system parameters information
)
Calculating address
:
addr=SW10 × 16
+
SW11
Data display
:
hex display, H means
hex number
0
1
The EE data of address 001H
…
…
…
0
15
The EE data of address
00FH
1
0
The EE data of address 010H
…
…
…
1
15
The EE data of address
01FH
…
…
…
15
15
The EE data of address FFH
13
0
0
The EE data of address 100H The last 256 bytes data display of local
EE
(
Failure information
)
Calculating address
:
addr=SW10 × 16
+
SW11
Data display
:
hex display, H means
hex number.
When the dial-up wheel is on 13 0 0
,
press SW2(UP) for 2 seconds, then the
last 256 bytes of EE will be cleared.
0
1
The EE data of address 101H
……
…… ……
1
15
The EE data of address 11FH
……
…… ……
15
15
The EE data of address
1FFH