33
Electric wiring and the application
SW11 Function
Display with digital tube LED1
~
4
3
Indoor unit
communication
checking and program
version
If communication is normal, show the indoor unit program
version (one decimal). If communication stops, normally show
“0000”
(
failing communication for 5 consecutive rounds
)
. If
communication has been abnormal, show “----”.
For example,“U4.2” means indoor unit version is V4.2.
4
Indoor unit fault
Show indoor unit fault code. If no fault, show 0.
5
Indoor unit capacity
Indoor unit capacity
(
Unit
:
HP
,
one decimal
),
1.5 HP show 1.5
6
Indoor unit expansion
valve open angle
Expansion open angle
(
Unit: pls
)
7
Indoor unit
environment temp. Tai Ambient temperature
(
Unit:
℃)
8
Indoor unit gas pipe
temp. Tc1
Gas pipe temperature
(
Unit:
℃)
9
Indoor unit liquid temp.
Tc2
Liquid pipe temperature
(
Unit:
℃)
10
Indoor unit startup
mode, actual running
speed and SCODE
code
LED1 means startup mode, O
:
stop/ C
:
cooling/ H
:
heating
LED2 means indoor units actual running speed
(
0-stop
,
1-low
speed
,
2-medium speed
,
3-high speed
),
LED3 and LED4 means SCODE code
(
0
~
15
)
.
For example, C311 mean high cooling speed
,
SCODE is 11
.
11
Indoor Unit temp.
setting Tset
Temperature setting
(
Unit:
℃)
12
Wrong wiring
inspection
0 means no failure
,
79 means wiring connection failure
(
indoor
no display
)
13
Connected valve box
number
“----” means connecting to the valve box failed.
Press SW2(UP) for 2 seconds
,
show “CCCC”
,
forcible indoor
cooling start up
Press SW1(DOWN) for 2 seconds
,
show “OFF”
,
forcible
indoor shutdown
14
Solenoid valve status
of connected valve box
LED1
:
BS4WV
:
1 ON 0 OFF――Far left
LED2
:
BSSV1
:
1 ON 0 OFF
LED3
:
BSSV2
:
1 ON 0 OFF
LED4
:
BSSV3
:
1 ON 0 OFF
Showing “----”means not connected to the valve box;
Showing“E-”+failure code means there is failure.
Press SW2(UP) for 2 seconds
,
show“HHHH”
,
forcible indoor
heating start up;
Press SW1(DOWN) for 2 seconds
,
show“OFF”
,
forcible
indoor shutdown