28
Electric wiring and the application
Outdoor power source and power cable
• Power cable must be fixed firmly.
•
Each outdoor must be earthed well.
•
When power cable exceeds the range, thicken it appropriately.
Item
Model
Power
source
Power
cable
section
(mm
2
)
Wire
length
(m)
Circuit
breaker
(A)
Rated current of residual
circuit breaker(A)
Ground fault
interruptor(mA)
response time(S)
Ground wire
Section
(mm
2
) Screw
Individual power
AV08IMVUSA
3N~,
380-
400V,
50/60
Hz
6
60
40
40A 30mA below 0.1S
3.5
M5
10
60
40
40A 30mA below 0.1S
3.5
M5
YCV335HR
10
60
60
60A 30mA below 0.1S
3.5
M5
YCV400HR
16
60
60
60A 30mA below 0.1S
3.5
M5
YCV450HR
16
60
70
70A 30mA below 0.1S
3.5
M5
VP Wiring nameplate
CN8
LED3
LED2
CN6
Qo Po
Connect
outdoor P&Q
Connect
indoor P&Q
To power supply
1PH,220-230V~,50/60Hz
Terminal Block for
Communication
Terminal Block
for Power
R
P Q
B
L N
C
R
W
B
B
Y
CN7
Qi Pi
CN3
SVB3
CN5
SVB2
CN2
SVB1
CN4
4WVBS
CN1
220V_L CN2
220V_N
SW03
DIP
ON
12
34
56
78
IC5
LED1
LX1
FUSE
T3.
15A
-250V
A
C
Notice:
The colours use these letters for short
W:White B:Black R:Red Y:Yellow