CONTROL SYSTEM
11-30
Revision 0
11.14
SPT Adjustment in Sleep Mode
•
In COOL, AUTO COOL or DRY modes, the SPT adjustment is positive
(from 0 to +3
o
C).
•
In HEAT or AUTO HEAT modes, the SPT adjustment is negative
(from 0 to -3
o
C).
•
In other modes, there is no SPT adjustment.
•
The SPT adjustment is cancelled when the Sleep mode is cancelled.
SPT
Time [Hr]
4
8
5
3
2
6
Start
Sleep
7
RT
SPT-1
SPT-2
SPT-3
SPT+2
SPT+1
SPT+3
1
7 Hours Sleep operation
for Normal Sleep Mode
Unit is turned to SB
after Sleep
Cool, Dry modes
Heat mode
NOTE
If OFF-timer is active, the unit may go to SB before or after 7 hours of
sleep operation.