CONTROL SYSTEM
11-34
Revision 0
d. STEP 3: AUTO LED WALK TEST.
1) All the LEDS will turn OFF.
2) All the LEDS will turn ON for 1 second one by one in the following sequence:
STAND-BY
ð
OPERATE
ð
TIMER
ð
FILTER
ð
COOL
ð
HEAT.
3) In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 °c
ð
20 °c
ð
22 °c
ð
24 °c
ð
26 °c
ð
28 °c
ð
30 °c
ð
High IFAN
ð
Auto IFAN
ð
Med IFAN
ð
Low IFAN
ð
STAND-BY
ð
TIMER
ð
FILTER
ð
COOL
ð
HEAT.
e. STEP 4: AUTO REALY WALK TEST:
All relays will energize one by one in the following sequence:
COMPRESSOR
ð
OUTDOOR FAN
ð
R. V.
ð
HEATER 1
ð
HEATER 2
ð
INDOOR WATER PUMP
ð
SWING or OUTDOOR WATER PUMP
ð
INDOOR
FAN: LOW
ð
MID
ð
HIGH.
When the relay walk test is completed, the next test will start automatically.
f. STEP 5: FREQUENCY TESTING:
If the frequency measuring process fails the COOL LED will turn ON. In order to
move to the next step, press ON/OFF button on the remote control.
g. STEP 6: INPUT TEST.
The test purpose is to check the analog real time indicators (thermistors, LEVEL
and clock) according to the table below.
LED Indicator
Condition for LED to be ON
STBY LED
Room thermistor
≠
25°c
OPER LED
Indoor coil thermistor
≠
25°c
TIMER LED
Outdoor coil thermistor
≠
25°c
FILTER LED
Clock
COOL LED
LEVEL 2&3
HEAT LED
LEVEL 4
h. STEP 7: TIMING RESET TEST (WATCH DOG).
The test purpose is to verify that the CPU rise time after power failure is between 1
to 3 sec, test results are indicated on the LEDS : STAND-BY,OPER, TIMER and
FILTER turning ON one by one.
The results of the test are coded as follows:
Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON
Summary of Contents for K XLN24 RC 3PH
Page 12: ...OUTLINE DIMENSIONS Revision 0 4 1 4 OUTLINE DIMENSIONS 4 1 K XLN 24 30...
Page 13: ...OUTLINE DIMENSIONS 4 2 Revision 0 4 2 Outdoor Unit OU724 4 3 Outdoor Unit OU830...
Page 29: ...WIRING DIAGRAMS Revision 0 7 3 7 5 Outdoor Unit OU724 OU830 3PH...
Page 31: ...ELECTRICAL CONNECTIONS 8 2 Revision 0 8 3 K XLN 24 30 3PH...
Page 33: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 9 1 2 K XLN 30 R410A...
Page 34: ...REFRIGERATION DIAGRAMS Revision 0 9 3 9 2 Cooling Only Models 9 2 1 K XLN 24 30...
Page 37: ...CONTROL SYSTEM 11 2 Revision 0 11 1 3 Main PCB Controller...
Page 78: ...EXPLODED VIEWS AND SPARE PARTS LIST Revision 0 13 5 13 3 Exploded view of outdoor unit ONG...
Page 79: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 6 Revision 0...