TROUBLESHOOTING
12-2
Revision 0
No.
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
11
One of the protections is
activated and compressor
is stopped with no
apparent reason.
Control problem or
refrigeration system
problem.
Perform diagnostics to detect
active protection, and take
action accordingly.
12
Compressor motor is noisy
and no suction is present.
Wrong phase order to
compressor.
Check compressor phase
order.
13
Water leakage from indoor
unit.
Indoor unit drainage tube
is blocked.
Check and open drainage
tube.
14
Freezing of outdoor unit in
HEAT Mode and outdoor
unit base is blocked with
ice.
Connect base heater.
15
Unit operates with wrong
fan speeds or wrong
frequency.
Wrong jumper settings.
Perform diagnostics to obtain
unit model or if operating by
EEPROM parameters.
16
Filter LED comes ON after
512 hours of operation
Clogged air-filter
Replace air-filter. Press the
RESET button.
Summary of Contents for K XLN24 RC 3PH
Page 12: ...OUTLINE DIMENSIONS Revision 0 4 1 4 OUTLINE DIMENSIONS 4 1 K XLN 24 30...
Page 13: ...OUTLINE DIMENSIONS 4 2 Revision 0 4 2 Outdoor Unit OU724 4 3 Outdoor Unit OU830...
Page 29: ...WIRING DIAGRAMS Revision 0 7 3 7 5 Outdoor Unit OU724 OU830 3PH...
Page 31: ...ELECTRICAL CONNECTIONS 8 2 Revision 0 8 3 K XLN 24 30 3PH...
Page 33: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 9 1 2 K XLN 30 R410A...
Page 34: ...REFRIGERATION DIAGRAMS Revision 0 9 3 9 2 Cooling Only Models 9 2 1 K XLN 24 30...
Page 37: ...CONTROL SYSTEM 11 2 Revision 0 11 1 3 Main PCB Controller...
Page 78: ...EXPLODED VIEWS AND SPARE PARTS LIST Revision 0 13 5 13 3 Exploded view of outdoor unit ONG...
Page 79: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 6 Revision 0...