PERFORMANCE DATA
Revision 0
5-1
5.
PERFORMANCE
DATA
5.1
K
XLN24
OU724
R410A 1PH/3PH
5.1.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR WB/DB ID COIL (
°
C)
ENTERING AIR
DB OD COIL (
°
C)
DATA
15/21 17/24 19/27 21/29 23/32
TC
6.91
7.31
7.65
7.99
8.26
SC
4.74
5.02
5.29
5.17
5.26
15
(1)
PI
1.60
1.60
1.60
1.61
1.62
TC
6.84
7.24
7.58
7.92
8.19
SC
4.88
5.18
5.47
5.31
5.43
20
(1)
PI
1.73
1.73
1.74
1.76
1.76
TC
6.57
7.04
7.45
7.79
8.06
SC
4.61
4.93
5.22
5.12
5.25
25
PI
1.86
1.88
1.90
1.91
1.91
TC
6.16
6.63
7.18
7.45
7.72
SC
4.38
4.73
5.10
5.00
5.21
30
PI
2.02
2.04
2.07
2.08
2.09
TC
5.69
6.16
6.77
7.11
7.38
SC
4.12
4.48
4.90
4.84
5.04
35
PI
2.18
2.21
2.25
2.27
2.28
TC
5.15
5.62
6.23
6.57
6.84
SC
3.83
4.21
4.63
4.56
4.78
40
PI
2.35
2.39
2.43
2.45
2.47
TC
4.47
4.94
5.55
5.89
6.16
SC
3.48
3.86
4.35
4.26
4.46
46
PI
2.58
2.62
2.66
2.70
2.73
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI
–
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD
– Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories.
Summary of Contents for K XLN24 RC 3PH
Page 12: ...OUTLINE DIMENSIONS Revision 0 4 1 4 OUTLINE DIMENSIONS 4 1 K XLN 24 30...
Page 13: ...OUTLINE DIMENSIONS 4 2 Revision 0 4 2 Outdoor Unit OU724 4 3 Outdoor Unit OU830...
Page 29: ...WIRING DIAGRAMS Revision 0 7 3 7 5 Outdoor Unit OU724 OU830 3PH...
Page 31: ...ELECTRICAL CONNECTIONS 8 2 Revision 0 8 3 K XLN 24 30 3PH...
Page 33: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 9 1 2 K XLN 30 R410A...
Page 34: ...REFRIGERATION DIAGRAMS Revision 0 9 3 9 2 Cooling Only Models 9 2 1 K XLN 24 30...
Page 37: ...CONTROL SYSTEM 11 2 Revision 0 11 1 3 Main PCB Controller...
Page 78: ...EXPLODED VIEWS AND SPARE PARTS LIST Revision 0 13 5 13 3 Exploded view of outdoor unit ONG...
Page 79: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 6 Revision 0...