CONTROL SYSTEM
Revision 0
11-11
11.5
Heating
Mode
11.5.1
Heating Mode - General
a. Compensation Procedure
When I-FEEL is OFF during HEAT mode: RT= RAT – CTV.
When I-FEEL is ON during HEAT mode: RT= RCT.
Type of Indoor
CTV
Wall Mounted
+3
o
C
Mobiles / Floor Ceiling
+0
o
C
Square /Window
+2
o
C
Ducted
+4
o
C
Cassettes
+4
o
C
No compensation will be activated in Forced operation modes
b. IFAN operation rules for RC and SH groups:
1) As a general rule for
RC and SH groups,
IFAN will be switched ON according
to the following graph:
NOTE 1
When COMP is ON (except WAX Model), IFAN will change from
LOW to OFF either when:
a) ICT<28 and IFAN is on for 5 min or longer.
Or,
b) ICT<20
NOTE 2
When ICT is faulty:
When the compressor switches from OFF to ON (excluding
deicing), IFAN will be on in ANY speed.
When the compressor switches from ON to OFF, the IFAN will
change to LOW speed for 30 seconds and then it will be off.
2) In SH or RC group, IFAN will operate for Min 30 sec according to 1) above
after HEs are turned off, where in a case it has to be OFF, it will be forced to
LOW speed.
30
17
32
20
ANY
LOW
OFF
IFAN
ICT
40
25
Ducted
General:
Window:
Note 1
Summary of Contents for K XLN24 RC 3PH
Page 12: ...OUTLINE DIMENSIONS Revision 0 4 1 4 OUTLINE DIMENSIONS 4 1 K XLN 24 30...
Page 13: ...OUTLINE DIMENSIONS 4 2 Revision 0 4 2 Outdoor Unit OU724 4 3 Outdoor Unit OU830...
Page 29: ...WIRING DIAGRAMS Revision 0 7 3 7 5 Outdoor Unit OU724 OU830 3PH...
Page 31: ...ELECTRICAL CONNECTIONS 8 2 Revision 0 8 3 K XLN 24 30 3PH...
Page 33: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 9 1 2 K XLN 30 R410A...
Page 34: ...REFRIGERATION DIAGRAMS Revision 0 9 3 9 2 Cooling Only Models 9 2 1 K XLN 24 30...
Page 37: ...CONTROL SYSTEM 11 2 Revision 0 11 1 3 Main PCB Controller...
Page 78: ...EXPLODED VIEWS AND SPARE PARTS LIST Revision 0 13 5 13 3 Exploded view of outdoor unit ONG...
Page 79: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 6 Revision 0...