5-5
PERFORMANCE DATA & PRESSURE CURVES
SM HAFRPM 1-A.3 GB
5.3
HAF 9 / GCN 9
5.3.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
2.69
2.78
2.85
2.92
2.96
SC
1.91
1.99
2.07
2.12
2.16
PI
0.60
0.60
0.61
0.61
0.61
20
(1)
TC
2.60
2.74
2.83
2.89
2.96
SC
1.87
1.97
2.06
2.11
2.15
PI
0.65
0.66
0.66
0.66
0.66
25
TC
2.46
2.66
2.79
2.88
2.95
SC
1.82
1.93
2.04
2.10
2.14
PI
0.71
0.71
0.72
0.72
0.73
30
TC
2.30
2.51
2.71
2.80
2.89
SC
1.77
1.88
2.00
2.05
2.09
PI
0.76
0.77
0.78
0.79
0.79
35
TC
2.13
2.31
2.55
2.68
2.80
SC
1.68
1.80
1.95
2.01
2.05
PI
0.82
0.84
0.85
0.86
0.86
40
TC
1.94
2.11
2.30
2.52
2.65
SC
1.58
1.70
1.84
1.90
1.94
PI
0.89
0.90
0.92
0.93
0.94
46
TC
1.68
1.84
2.02
2.23
2.41
SC
1.46
1.56
1.68
1.74
1.78
PI
0.97
0.98
1.01
1.02
1.03
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.