5-17
PERFORMANCE DATA & PRESSURE CURVES
SM HAFRPM 1-A.3 GB
5.9
Model: HAF 9 / ONG3-9
5.9.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
2.71
2.81
2.87
2.94
2.98
SC
1.88
1.96
2.04
2.09
2.13
PI
0.53
0.53
0.53
0.53
0.54
20
(1)
TC
2.62
2.76
2.85
2.92
2.98
SC
1.84
1.94
2.02
2.08
2.12
PI
0.58
0.58
0.58
0.58
0.59
25
TC
2.48
2.68
2.81
2.90
2.97
SC
1.80
1.91
2.01
2.07
2.11
PI
0.62
0.63
0.63
0.64
0.64
30
TC
2.32
2.52
2.73
2.82
2.91
SC
1.74
1.85
1.97
2.02
2.06
PI
0.67
0.68
0.69
0.69
0.70
35
TC
2.15
2.33
2.57
2.70
2.83
SC
1.65
1.77
1.92
1.98
2.01
PI
0.73
0.74
0.75
0.76
0.76
40
TC
1.95
2.13
2.32
2.54
2.67
SC
1.56
1.68
1.82
1.87
1.91
PI
0.78
0.80
0.81
0.82
0.83
46
TC
1.69
1.85
2.04
2.25
2.42
SC
1.44
1.54
1.66
1.71
1.75
PI
0.86
0.87
0.89
0.90
0.91
LEGEND
TC –
Total Cooling Capacity, kWv
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).