7-1
ELECTRICAL DATA
SM HAFRPM 1-A.3 GB
7.
ELECTRICAL DATA
7.1
Single Phase Units
MODEL
HAF 7
HAF 9
Power Supply
To indoor
To indoor
1PH-230V-50Hz
1PH-230V-50Hz
Max Current, A
4.1
6.5
Circuit Breaker,A
10
10
Power Supply Wiring No. X
Cross Section mm
2
3x1.0 mm
2
3x1.0 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
5x1.0 mm
2
+2x0.5 mm
2
(OCT senser)
5x1.0 mm
2
+2x0.5 mm
2
(OCT senser)
Interconnecting Cable ST
Model No. X Cross Section mm
2
4x1.0 mm
2
4x1.0 mm
2
MODEL
HAF 12
Power Supply
To indoor
1PH-230V-50Hz
Max Current, A
7.7
Circuit Breaker,A
10
Power Supply Wiring No. X
Cross Section mm
2
3x1.0 mm
2
Interconnecting Cable RC
Model No. X Cross Section mm
2
5x1.0 mm
2
+2x0.5 mm
2
(OCT senser)
Interconnecting Cable ST
Model No. X Cross Section mm
2
4x1.0 mm
2
NOTE
Power wiring cord should comply with local lows and electrical
regulations requirements.