5-1
PERFORMANCE DATA & PRESSURE CURVES
SM HAFRPM 1-A.3 GB
5.
PERFORMANCE DATA & PRESSURE CURVES
5.1
HAF 7 / CON 7
5.1.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
2.12
2.19
2.25
2.30
2.33
SC
1.57
1.63
1.7
1.74
1.77
PI
0.49
0.49
0.49
0.49
0.49
20
(1)
TC
2.05
2.16
2.23
2.28
2.33
SC
1.54
1.62
1.69
1.74
1.77
PI
0.53
0.53
0.53
0.54
0.54
25
TC
1.94
2.09
2.20
2.27
2.32
SC
1.5
1.59
1.67
1.72
1.75
PI
0.57
0.58
0.58
0.59
0.59
30
TC
1.81
1.97
2.13
2.21
2.27
SC
1.45
1.54
1.64
1.69
1.72
PI
0.62
0.63
0.63
0.64
0.64
35
TC
1.68
1.82
2.01
2.11
2.21
SC
1.38
1.48
1.60
1.65
1.68
PI
0.67
0.68
0.69
0.7
0.70
40
TC
1.53
1.66
1.81
1.98
2.09
SC
1.30
1.40
1.51
1.56
1.59
PI
0.72
0.73
0.74
0.75
0.76
46
TC
1.32
1.45
1.59
1.76
1.90
SC
1.20
1.28
1.38
1.43
1.46
PI
0.79
0.80
0.82
0.83
0.84
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.