9 - MAINTENANCE
9.9 WATER FILTER
Verify that there are no impurities that obstruct the smooth
passage of water:
1)
Remove panel (
A
)
2)
Predispose a tray to collect the water;
3)
Turn off the shutoff cocks;
4)
Discharge the water
5)
Turn ON bleed bibcock (
C
)
6)
Unscrew the plug and check the filter
7)
Insert the filter and screw the plug;
8)
Turn on the cocks
9)
Vent the unit through the vent valves (see water
connections).
B
Drain valve unit.
A
9.10 AIR FILTER
It is very important for the air treatment coil to be able to offer
maximum thermal exchange.
•
Therefore, the unit must always operate with the filters
installed and clean.
•
Cleaning and replacement of filters are very important in
terms of health and hygiene.
•
Operation with clogged filters leads to a reduction in the air
flow rate, resulting in malfunctions and unit shutdowns. It
may even cause the unit to break down.
How often the filters need to be checked depends on the
quality of outdoor air, unit operating hours, dust and number of
persons in the rooms.
As a guideline, cleaning should ideally take place between
weekly and monthly. It is advisable to start with frequent
checks, and to adjust the frequency based on how much dirt is
discovered.
9.11 FILTER EXTRACTION
Extraction from the side
Extraction from the bottom
Minimum space for filter extraction.
Min. 660mm.
9.12 EXTRACTION THE FAN
To remove the fan:
1 - Unscrew the screws.
A
;
2 - Remove the fan:
3 - Unscrew the screws
B
fan support;
A
A
A
A
B
B
C