8 - CONTROL
8.3
UNIT PARAMETERS
The parameters accessible by password or supervision system can be modified only by qualified personnel after having read the spe-
cific manuals of the electronic system and of the supervision protocols.
Incorrect modifications can cause malfunctioning or damages.
GROUPE
ID MNEMONICO DESCRIPTION
SET
PA01 SetpointComfort
Point
de
consigne confort (default)
PA02
MaxSet
Max configurable set, both Eco and Confort
PA03
MinSet
Min configurable set, both Eco and Confort
PA04
SetCoolEco
Standard Set Eco in Cool
PA05
SetHeatEco
Standard Set Eco in Heat
PA06
MaxOffsetSet
Max. correction accepted to the set point from the thermostat
PA07
ZonaNeutraComfort
Neutral zone for the Auto mode in confort
PA08 ZonaNeutraEco
Neutral
zone
for the Auto mode in Eco
PA09
IsteresiHeat
Thermoregulation hysteresis in Heat
PA10
IsteresiAux
Thermoregulation hysteresis in Heat for Aux
PA11 IsteresiCool
Thermoregulation hysteresis in Cool
PA12
FBandIsteresiEco
Value to sum to thermoregulation hysteresis when ECO mode is active
PA13
TimerOverride
Random time between 0 and TimerOverride seconds for step insertion/release
SORG
PB01 SetLowSorgHeat Low
temperature thereshold source water
PB02
SetHiSorgCool
High temperature thereshold source water
PB03
IstLowTempSorg
Hysteresis for reset of high and low source temperature thereholds
PB04
MinApValvSorg
Min. source valve opening
PB05
MaxApValvSorg
Max. source valve opening
PB06
StartApValvSorg
Percentage of source valve opening at the start up
PB07
TStartValvSorg
Valve opening time at % StartApValvSorg source
UTIL
PC03
VccMinFanCool
Min voltage applicable to control 0-10 Vdc in Cool
PC04 VccMaxFanCool
Max
voltage
applicable to control 0-10 Vdc in Cool
PC05 VccMinFanHeat
Min
voltage applicable to control 0-10 Vdc in Heat
PC06 VccMaxFanHeat
Max
voltage
applicable to control 0-10 Vdc in Heat
PC07 RitCpDaFan
Compressor
activation delay from utility fan start
PC08
RitOffFanDaCp
Delay of utility fan stopping from compressor Off
PC09
RitOffFanDaAux
Delay of utility fan stopping from Off of the aux heater
PC16
MinFanAuxOn
Min percentage of utility fan if Aux=ON
CNF
PD05
SetAllLP
Low pressure alarm Set point from analogical input
PD06
DeltaAllLP
Hysteresis of low pressure alarm reset from analogical input
TARA
PE01
OffsetAI1
Setting of AI1 analogical input (Return Temperature I/O )
PE02
OffsetAI2
Setting of AI2 analogical input (Return Temperature from sensor thermostat)
PE03
OffsetAI3
Setting of AI3 analogical input (Output water Temperature source I/O )
PE04
OffsetAI4
Setting of AI4 analogical input (Exchanger Temperature treatment coil utility I/O )
PE05
OffsetAI5
Setting of AI5 analogical input (Electronic thermostatic return Temperature )
PE06
OffsetAI6
Setting of AI6 analogical input (High/low Pressure )
PE07
OffsetAI7
Setting of AI7 analogical input (Electronic thermostatic return pressure )
PE08
OffsetAITer
Setting of the ambient probe analogical input on thermostat board
BMS *
PF01 AddressTh
ModBus
address
of the thermostat (Slave)
PF02 BaudRateTh
Serial
communication
speed
for thermostat 0=2400 1=4800 2=9600 3=19200
PF03
ParityTh
Thermostatparity 0=No 1= Odd 2=Even
PF04
Address
ModBus address of the WLHP for the supervisor
PF05
BaudRate
Communication speed of the supervision serial 0=2400 1=4800 2=9600 3=19200
PF06
Parity
Parity of the supervision serial 0=No 1= Odd 2=Even
U.M.
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
sec.
°C
°C
°C
%
%
%
sec.
%
%
%
%
sec.
sec.
sec.
%
bar
bar
°C
°C
°C
°C
°C
bar
bar
°C
-
-
-
-
-
-
*
the modification of these parameters makes impossible the communication between thermostat and unit
Summary of Contents for DFO 5 - 9 - 17
Page 17: ...6 ELECTRICAL CONNECTIONS 6 3 ELECTRIC PANEL SIZES 5 9 ELECTRIC PANEL SIZES 17 X1 X1 A B A B C2...
Page 24: ...6 ELECTRICAL CONNECTIONS...
Page 43: ...NOTES...
Page 44: ...NOTES...