Electrical Control Function
216
Electrical Control System
---T3>60
℃
for 5 seconds, the compressor will stop until T3<52
℃
.
For other models: When T3≥65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor
will restart.
1.3.3 Heating Mode
1.3.2.1 Outdoor PMW open angle control
The unit is working in heating mode with the EXV open 300P(For 12K,it is 480P) for 3 minutes, then
adjusting PMW open angle according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
T4
E
DC_FAN_SSLOW_SPD_ADD
D
DC_FAN_SLOW_SPD_ADD
C
DC_FAN_MIN_SPD_ADD
B
DC_FAN_MID_SPD_ADD
A
DC_FAN_HI_SPD_ADD
21℃
19℃
18℃
16℃
15℃
13℃
12℃
10℃
1.3.3.3 Indoor fan running rules:
For XAD012:
In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold- wind
function has the priority.
When the compressor is running, the indoor fan is controlled as below:
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Summary of Contents for AWAU-YLD012-H11
Page 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 15: ...Service Space 136 Console Type 3 Service Space ...
Page 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Page 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Page 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...