Troubleshooting
Electrical Control System
237
2.4.2 For the unit with TWINS function(For the super-slim cassette & A5 duct)
2.4.2.1 Communication
malfunction
between master unit and indoor unit
F3 Displayed
F3 Displayed
Communication failure between
master unit and slave unit
Communication failure between
master unit and slave unit
Check the dial switch settings of
master unit and slave unit, is it right?
Check the dial switch settings of
master unit and slave unit, is it right?
Correct the
settings
Correct the
settings
No
Check the PQE communication wires
connection, is it good enough?
Check the PQE communication wires
connection, is it good enough?
Yes
Correct the wire
connections
Correct the wire
connections
No
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one caused E1 error code
is defective
One of the 2 indoor PCBs is defective.
Connect only one indoor unit to the outdoor
unit separately. The one caused E1 error code
is defective
Yes
Problem is solved
Problem is solved
2.4.2.2 Other malfunction between master unit and indoor unit
One indoor unit displays ”F4”, which means another indoor unit is faulty. Check another indoor unit’s error
code and then follow the appropriate solutions to solve the malfunction.
Summary of Contents for AWAU-YLD012-H11
Page 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 15: ...Service Space 136 Console Type 3 Service Space ...
Page 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Page 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Page 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Page 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...